This unit meets the requirements of NFPA 101 for Periodic Testing of Emergency
Lighting Equipment.  It provides visual indication of unit malfunctions including:

SELF-TESTING / SELF-DIAGNOSTICS

Battery Fault

Charger Fault

Transfer Fault

Lamp Fault

Door Fault

SELF-TEST

An automatic self-test and diagnostic function will be performed every 28 days.  A load
test will be performed for 30 seconds checking for a lamp, battery or transfer fault.  On
every forth test, the load test will follow a door function test, during which the door will
open for approximately 1 second and then close, without the lamps turning on.  This
automatic self-test and diagnostic function will be performed only if the battery is fully
charged.  If not, the test will automatically reschedule.  The charger function is
monitored continuously.

USER-TEST

A manual USER-TEST can be performed for 30 seconds or 90 minutes.  By pushing the
“TEST” Switch for 1 second, the door will open and the lamps will illuminate for 30
seconds.  If the “STATUS” indicator shows GREEN indicating a fully charged Battery and
the Switch is pushed for 4 seconds, the door will open and the lamps will illuminate for
90 minutes.  If the Battery is not fully charged, the 30 second test will run.

In either mode, the USER-TEST can be cancelled by pushing and holding the “TEST”
Switch for 1 second after the lamps con on.

LAMP LOAD LEARN

The self-diagnostic system “learns” the lamp load during the first test.  Subsequent tests
compare the measured lamp load during the test to the learned lamp load values.

CLEARING FAILURE INDICATIONS

Failure indications can be cleared by correcting the indicated fault and pushing and
holding the “TEST” Switch for 1 second.

STATUS INDICATIONS

Status indications for the self-testing / self-diagnostic system are shown on the
following page.

Page 7

Summary of Contents for Aperion LED

Page 1: ...ng by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Servicing of this eq...

Page 2: ...re supplied by others UNIT IS APPROVED FOR TYPE ICINSTALLATION Alignbackboxsolampheadopeningisflush orslightlybehindinnersurfaceofceilingorwall ROUGH IN CEILING AND WALL MOUNT SUPPORTING MEMBERS MUST...

Page 3: ...ved wire clamp and make connections using wire nuts supplied Connect wires per local codes Connect to transformer as follows Feed transformer secondary cable with connector through hole in splice box...

Page 4: ...UPPLIED WITH A CHOICE OF 3 TYPES OF BATTERY SOURCES SEALED LEAD CALCIUM LC NICKEL CADMIUM Ni Cd NICKEL METAL HYDRIDE Ni MH NOTE Disconnected Battery must be recharged within 120 days Attach Battery Ca...

Page 5: ...with pivoting door Latch Tabs Push door open to access Spring Latch Bar Spring Latch Bar Insert Phillips screwdriver into hole as shown push down and forward to engage latches NOTE Once Battery is co...

Page 6: ...lly Recessed Emergency Light has an adjustable LED assembly mounted on the moveable door For wall mounting the LED assembly should be aimed down towards the floor For ceiling mounting the LED assembly...

Page 7: ...usly USER TEST A manual USER TEST can be performed for 30 seconds or 90 minutes By pushing the TEST Switch for 1 second the door will open and the lamps will illuminate for 30 seconds If the STATUS in...

Page 8: ...Replace Battery Factory Service Check for Paint Seal Replace Lamp For 90 minute User Tests wait for full charge For 30 second User Tests try again after an hour of charging Page 8 BATTERY The battery...

Reviews: