Management of technical room fan output and ON-OFF output
–
If one of the available outputs is configured as “technical room fans” (value set to 11), the fans are always on
(except for models with J/K thermocouples, where they are activated when the threshold set by parameter r37
is exceeded).
–
–
If one of the available outputs is configured as “ON-OFF” (value set to 14), the relay will operate as follows:
–
OFF when the device is on stand-by mode
–
ON under all other conditions
Management of the auxiliary relay
–
If one of the available outputs is configured as “AUX” (value set to 15), the label “AUX” will be displayed above the
fourth function key (otherwise it is not displayed).
–
The color is grey when the relay is ON
and switches to green when the relay is OFF
.
–
The relay status can be changed touching the fourth function key or through the push-encoder as described in the
introduction