EVAPCO PHC-D-E Rigging & Assembly Instructions Download Page 8

8

PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS

Final Assembly & Startup Details 

Shipping Materials

Remove any wood chocks, spare parts, or miscellaneous items that have been placed inside the unit for shipping purposes. Clean all 

debris from the basin.

Pump Discharge Line

Connect the riser pipe from the pump discharge on the basin section to the riser pipe on the coil / fan section using the flexible 

connection and hose clamps provided.

Makeup Water Line

Connect (plumb) the makeup water source to the makeup water connection on the unit. The makeup water supply pressure to the 

unit should be maintained between 20 and 50 psig (140 kPa and 340 kPa). Water supply pressure in excess of 50 psig (340 kPa) may 

damage the mechanical float valve.

Bleed or Blowdown

EVAPCO recommends an automated conductivity controller to maximize the water efficiency of your system.  Based on 

recommendations from the selected water treatment company, the conductivity controller should open and close a motorized ball or 

solenoid valve to maintain the conductivity of the recirculating water.  If the manual valve provided in the bleed-off line on a unit with 

factory supplied pump(s) is used to control the rate of bleed, it should be set to maintain the conductivity of the recirculating water 

during periods of peak load at the maximum level recommended by the selected water treatment company. If no direction is provided, 

the valve should be fully open. On units shipped without a pump (remote sump applications), the bleed-off arrangement and valve 

must be provided by the customer.

Float Valve Adjustment

The float valve is preset at the factory however adjustment should be checked after rigging. The float valve should be adjusted so that 

the center of the float is 1” below the center of the overflow connection when the valve is in the fully closed position. Raise or lower the 

float by using the wing nuts on the vertical threaded rod. Do not adjust the horizontal rod.

During normal operation, the water level will drop 3” (76 mm) to 4” (102 mm) below the overflow.

Strainer

Check the strainer in the basin to ensure that it is in its proper location over the pump suction.

Screens

Protective screens are provided across the top of the fan cylinders on all models. Inspect the screens to ensure there are no gaps that 

may present a safety hazard. Check all screen fasteners to ensure they are tight and secure.

Fan Rotation

Bump start and check the fans for proper rotation. Directional arrows are placed on the inside of the axial fan cylinders.

Pump Rotation

After filling the basin to the overflow with fresh water, bump start and check the pump for proper rotation. Directional arrows are found 

on the pump impeller housing. 

Do not start pumps prior to filling the basin with water. Dry pump operation will damage the pump 

seals.

Maintenance

Once installation is complete and the unit is turned on, it is important that it be properly maintained. Maintenance is not difficult or 

time consuming but must be done regularly to assure maximum trouble free performance of the unit. Refer to the “Operation and 

Maintenance Instructions” bulletin enclosed with the unit for proper maintenance procedures.

Also, proper freeze protection must be provided if the unit is located in a cold climate. Refer to the “Operation and Maintenance 

Instructions” bulletin supplied as well as factory product bulletins for further information.

Summary of Contents for PHC-D-E

Page 1: ...PHC E SERIES Rigging Assembly Instructions FORCED DRAFT EVAPORATIVE CONDENSERS...

Page 2: ...allation practices prior to rigging and assembly The information in this bulletin is for informational purposes only These instructions do not purport to cover all variations and possible contingencie...

Page 3: ...has not been altered Should the field inspection indicate the section alignment square has been altered please contact the factory or your local EVAPCO sales representative for additional instruction...

Page 4: ...to PHC S1182 PHC D621 to PHC D2050 PHC L463 to PHC L842 AIR IN AIR IN A AIR IN AIR IN AIR IN AIR IN C B Figure 1 Recommended Steel Support for S Models Figure 2 Recommended Steel Support for D Models...

Page 5: ...ting points should be used for final positioning only and for lifting where no danger exists If they are used for extended lifts safety slings and spreader bars should be provided under the sections a...

Page 6: ...ECTION S AS SHOWN IN FIGURES 7 and 8 The bottom of the spreader beam must be a minimum dimension H above the lowest lifting ear to prevent undue strain on the lifting ears and the section structure Th...

Page 7: ...isturbed Place drift pins see Figure 9 in at least three of the corner mounting holes and gradually lower the coil section into place using the drift pins to guide the section down accurately onto the...

Page 8: ...ve is preset at the factory however adjustment should be checked after rigging The float valve should be adjusted so that the center of the float is 1 below the center of the overflow connection when...

Page 9: ...esult of improper water treatment control during the startup of new equipment The initial commissioning and passivation period is critical for maximizing the service life of galvanized equipment EVAPC...

Page 10: ...10 PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS NOTES...

Page 11: ...11 PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS NOTES...

Page 12: ...Inc Edwardsville KS USA 913 322 5165 marketing evaptech com Tower Components Inc A wholly owned subsidiary of EVAPCO Inc Ramseur NC USA 336 824 2102 mail towercomponentsinc com EVAPCO Alcoil Inc A wh...

Reviews: