4
PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS
Rigging Basin Section
Lifting devices are located in the lower corners of the basin section for lifting and final positioning purposes as shown in
Figures 3
and
4
. The bottom of spreader beam must be a minimum dimension of “H” above the lowest lifting ear to prevent undue strain on the lifting
devices. See
Table 2
for the minimum “H” dimension. These lifting devices should not be used for extended lifts or where any hazard
exists unless safety slings are employed under the section.
(See “Extended Lifts” section for proper arrangement.)
Bolt the basin section
to the steel support before rigging the coil / fan section.
PHC-S208 to PHC-S1182
PHC-D621 to PHC-D2050
PHC-L463 to PHC-L842
AIR IN
AIR IN
A
AIR IN
AIR IN
AIR IN
AIR IN
C
B
Figure 1
— Recommended Steel Support for S Models
Figure 2
— Recommended Steel Support for D Models
PHC-S-E Models
PHC-D-E Models
Table 1
— Recommended Steel Support
PHC-E Pan Footprint Dimensions
Box Size
A
B
C
S Models
7x9
86” (2184 mm)
-
-
7x12
86” (2184 mm)
-
-
7x18
86” (2184 mm)
-
-
12x12
142” (3607 mm)
-
-
12x18
142” (3607 mm)
-
-
12x24
142” (3607 mm)
-
-
12x36
142” (3607 mm)
-
-
D Models
12x24
-
288” (7315 mm)
144” (3658 mm)
14x26
-
312” (7925 mm)
156” (3962 mm)
24x24
-
288” (7315 mm)
144” (3658 mm)
28x26
-
312” (7925 mm)
156” (3962 mm)
Table 2
— Dimensions for Basin Sections
Section Size - Unit Type
H
W
7 x 9 - S
8’ 10” (2692 mm)
7’ 4” (2235 mm)
7 x 12 - S
11’ 8” (3556 mm)
7’ 4” (2235 mm)
7 x 18 - S
16’ 11” (5156 mm)
7’ 4” (2235 mm)
12 x 12 - S
11’ 8” (3556 mm)
12’ (3.6 m)
12 x 18 - S
16’ 11” (5156 mm)
12’ (3.6 m)
12 x 24 - D
10’4” (3150 mm)
12’ (3.6 m)
14 x 26 - D
11’3” (3429 mm)
14’ (4.2 m)