background image

6

PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS

Applying Sealer Tape 

Once the bottom section has been set on the supporting steel and bolted in place, wipe the top flanges to remove any dirt or moisture. 

Place sealer tape over the mounting holes centerline on the side flanges. Apply two strips of sealer tape, one partially overlapping the 

other, on the end flanges. The sealer tape should overlap on the corners as shown in 

Figure 6

. Do not splice the sealer tape along the 

end flanges and preferably not on the side flanges if it can be avoided. Always remove the paper backing from the sealer tape. 

Rigging Coil / Fan Section 

Four lifting ears are provided in the upper corners of the coil / fan sections for lifting. Sections 24’ (7,3 m) or longer will have two 

additional lifting ears in the middle of the section (See 

Figures 7

 and 

8

).

 

CAUTION:  USE ALL LIFTING EARS PROVIDED ON THE SECTION. A SPREADER BEAM MUST BE USED FOR  

 

LIFTING THE TOP SECTION(S) AS SHOWN IN FIGURES 7 and 8!

The bottom of the spreader beam must be a minimum dimension 

“H” above the lowest lifting ear to prevent undue strain on the 

lifting ears and the section structure. The weight is not evenly 

distributed across the width of the coil/fan section. Therefore, 

the top connection of the spreader beam will need to be offset 

towards the coil side to balance the load. The location of this 

connection will vary based on the unit configuration. 

See 

Table 3

 for the “H” and “W” dimensions. These lifting devices 

should not be used for extended lifts or where any hazard exists 

unless safety slings are employed under the section. 

(See “Extended Lifts” for proper arrangement)

W

A*

H

Figure 7

 

— S Model Coil / Fan Section 

9’ (2.7 m), 12’ (3.6 m) and 18’ (5.5 m) Long

W

H

Figure 8

 

— D Model Coil / Fan Section 

24’ (7.3 m) and 26’ (7.9 m) Long

Table 3

 — Dimensions for Coil / Fan Sections

Section Size - Unit Type

H

W

7 x 9 - S

8’ 10” (2692 mm) 7’ 4” (2235 mm)

7 x 12 - S

11’ 8” (3556 mm) 7’ 4” (2235 mm)

7 x 18 - S

16’ 11” (5156 mm) 7’ 4” (2235 mm)

12 x 12 - S

11’ 8” (3556 mm)

12’ (3.6 m) 

12 x 18 - S

16’ 11” (5156 mm)

12’ (3.6 m) 

12 x 24 - D

10’ 4” (3150 mm)

12’ (3.6 m) 

14 x 26 - D

11’ 3" (3429 mm)

14’ (4.2 m)

Summary of Contents for PHC-D-E

Page 1: ...PHC E SERIES Rigging Assembly Instructions FORCED DRAFT EVAPORATIVE CONDENSERS...

Page 2: ...allation practices prior to rigging and assembly The information in this bulletin is for informational purposes only These instructions do not purport to cover all variations and possible contingencie...

Page 3: ...has not been altered Should the field inspection indicate the section alignment square has been altered please contact the factory or your local EVAPCO sales representative for additional instruction...

Page 4: ...to PHC S1182 PHC D621 to PHC D2050 PHC L463 to PHC L842 AIR IN AIR IN A AIR IN AIR IN AIR IN AIR IN C B Figure 1 Recommended Steel Support for S Models Figure 2 Recommended Steel Support for D Models...

Page 5: ...ting points should be used for final positioning only and for lifting where no danger exists If they are used for extended lifts safety slings and spreader bars should be provided under the sections a...

Page 6: ...ECTION S AS SHOWN IN FIGURES 7 and 8 The bottom of the spreader beam must be a minimum dimension H above the lowest lifting ear to prevent undue strain on the lifting ears and the section structure Th...

Page 7: ...isturbed Place drift pins see Figure 9 in at least three of the corner mounting holes and gradually lower the coil section into place using the drift pins to guide the section down accurately onto the...

Page 8: ...ve is preset at the factory however adjustment should be checked after rigging The float valve should be adjusted so that the center of the float is 1 below the center of the overflow connection when...

Page 9: ...esult of improper water treatment control during the startup of new equipment The initial commissioning and passivation period is critical for maximizing the service life of galvanized equipment EVAPC...

Page 10: ...10 PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS NOTES...

Page 11: ...11 PHC PARALLEL HYBRID EVAPORATIVE CONDENSERS NOTES...

Page 12: ...Inc Edwardsville KS USA 913 322 5165 marketing evaptech com Tower Components Inc A wholly owned subsidiary of EVAPCO Inc Ramseur NC USA 336 824 2102 mail towercomponentsinc com EVAPCO Alcoil Inc A wh...

Reviews: