Mnemonic
Scrolling Display and description
Range
This section applies to the Timer only
– see also section 6.4
none
None
Dwel
Dwell
DeLy
Delayed switch on
TM.CFG
TIMER CONFIGURATION
Configures the timer type:- Dwell, Delay,
Soft Start or none. The timer type can only be changed when the
timer is reset..
sfst
Soft start
TM.RES
TIMER RESOLUTION
Selects the resolution of the timer. This can
only be changed when the timer is reset.
Hour
min
Hours
Minutes
THRES
TIMER START THRESHOLD
The timer starts timing when the
temperature is within this threshold of the setpoint. This provides a
guaranteed soak temperature. The threshold can be set to OFF in
which case it is ignored and the timing starts immediately.
If a setpoint ramping is set, then the ramp completes before the timer
starts.
OFF or 1 to 3000 units/minute
OFF
Control OP goes
to zero
Dwel
Control continues
at SP1
END.T
TIMER END TYPE
This determines the behaviour of the timer when it
has timed out. This value can be changed while the timer is running.
SP2
Go to SP2