Engineering Manual 2408
i Indicator
4.7.4
Calibration Parameters
CAL
Basic Indicator Calibration
Selected parameter
rCAL
Selected re-calibration
nonE
Idle state - no calibration performed
parameter
PV.1
Main process value input selected
PV.2
Second analogue input selected (this will always be in module
position 3)
1A.Hi
Module 1 DC retransmission high output (if installed)
1A.Lo
Module 1 DC retransmission low output (if installed)
2A.Hi
Module 2 DC retransmission high output (if installed)
2A.Lo
Module 2 DC retransmission low output (if installed)
3A.Hi
Module 3 DC retransmission high output (if installed)
3A.Lo
Module 3 DC retransmission low output (if installed)
If
rCAL
=
PV1
or
PV2
the following parameters
appear:
Calibration point
Calibration value
PV
PV
or
PV.2
calibration point
IdLE
Idle
mv.L
mV low calibration point selected
0.000 mV
mv.H
mV high calibration point selected
50.000 mV
V 0
0 Volt calibration point selected
0.000V
V 10
10 Volt calibration point selected
10.000V
CJC
Cold junction calibration
See below
rtd
Resistance input calibration
400.00
Ω
HI 0
High impedance input. 0 Volt calibration
point selected
0.000V
HI 1.0
High impedance input. 1.0 Volt
calibration point selected
1.000V
FACt
Restore factory calibration selected
GO
Start calibration
no
Waiting to calibrate PV point
YES
Start calibration
busy
Busy calibrating
done
Calibration complete
FaiL
Calibration failed
If
rCAL
=
1AHi
to
3aLo
(DC output module calibration) the following parameters appear:
cAL.L
DC output calibration low point
0
0
= Factory cal. Trim value to give output = + 1V or +2mA
cAL.H
DC output calibration high point
0
100
= Factory cal. Trim value to give output = + 9V or +18mA
4.7.5
Password Configuration
PASS
Passwords
Range
Notes
When passwords are changed please make a
note of the new numbers
Default
setting
Customer
setting
ACC.P
Full and Edit level password
0-
9999
Having once entered the correct password,
operator, full or edit level can be selected at
will. To return to operator level and lock the
indicator in this level, either switch the
indicator off and on again or enter an invalid
password as described in section 4.2.1.
1
cnF.P
Configuration level
password
0-
9999
Configuration level can only be entered from
the above level. You must exit this level to
return to operator level by following the exit
procedure in section 4.7.6.
2
CAL.P
User calibration password
0-
9999
User calibration level (described in Section
3.5.1.) can be entered from operator level.
To return to normal operation:
Enter an incorrect password
Switch power off and on again
3
4.7.6
To Leave Configuration Level
Do This
This Is The Display You Should See
Additional Notes
CAL
1.
Press
to reach the
<
exit
>
display
2.
Press
or
to select
<
YES
>
After 2 secs the display will blank then
return to the HOME display in Operator
level
YES
Exit
58