Engineering Manual 2408
i Indicator
3.3
Parameter Tables
3.3.1
HOME List
Mnem
-onic
Meaning
Adjustable Range
Default
setting
Customer
setting
dSP.F
HOME display front
See ‘HOME display options’
PV
dSP.b
HOME display back
section 2.1.2.
None
C.id
Customer defined identity number
0
to
9999
0
3.3.2
Alarm List
Mnem
-onic
Meaning
Adjustable Range
Default
setting
Customer
setting
1---
Alarm 1 setpoint
In place of dashes, the
last three letters
indicate the alarm type:
as shown in the
‘Alarm
Messages’
table section 2.2.4.
Between low and high setpoint
limits which are set in the
<
SP
>
list
Rate of change alarms are
direction sensitive from-9999
to +99999 units/sec or min
0
2---
Alarm 2 setpoint
0
3---
Alarm 3 setpoint
0
4---
Alarm 4 setpoint
0
If the alarm is disabled the parameter will not appear in this list
HY 1
Alarm 1 Hysteresis
Prevents relay ‘chatter’
by setting a difference
between the relay ON
and OFF points
1
to
99999
display units
1
HY 2
Alarm 2 Hysteresis
1
to
99999
display units
1
HY 3
Alarm 3 Hysteresis
1
to
99999
display units
1
HY 4
Alarm 4 Hysteresis
1
to
99999
display units
1
1dEL
Alarm 1 delay
Used to ignore
transient alarms.
Alarms must be true for
the delay time before
they become active
0
to
999.9
seconds
0
2dEL
Alarm 2 delay
0
to
999.9
seconds
0
3dEL
Alarm 3 delay
0
to
999.9
seconds
0
4dEL
Alarm 3 delay
0
to
999.9
seconds
0
In.AL
Inhibit alarm timer
To inhibit alarms for a
time, see section 4.5.5
On
/
OFF
OFF
InH.t
Time alarm
inhibited
0
to
999.9
seconds
0
3.3.3
Setpoint List
Mnem
-onic
Meaning
Adjustable Range
Default
setting
Customer
setting
L- r
Remote setpoint enable
Loc
Select local SP
Loc
rmt
Select remote SP
rm.SP
Remote master setpoint (for deviation alarms)
Displays remote SP value
N/A
Read only
rm.tr
Remote setpoint track.
OFF
No tracking
OFF
This parameter only appears if remote setpoint
has been configured
trAc
Local SP tracks
remote SP
SP 1
Local master setpoint value for deviation
alarms on input 1
SP1.L
to
Sp1.H
20
SP 2
Local master setpoint value for deviation
alarms on input 2
SP2.L
to
SPH.2
20
SP
Setpoint value when the combination of inputs
1 & 2 provide the measured value to the
indicator (for deviation alarms)
SPL
to
SPH
SP L
SP H
PV Alarms Setpoint low limit
Setpoint High limit
Input range min and max
(combination of input 1 2)
As per order
code
SP1.L
SP1.H
Input 1 Alarms Setpoint Low
Setpoint High
Between input 1 sensor range
min and max
As per order
code
SP2.L
SP2.H
Input 2 Alarms Setpoint Low
Setpoint High
Between input 2 sensor range
min and max
As per order
code
20
AL
SP
18