Engineering Manual 2408
i Indicator
3.3.5.3
Calibration Type = Comparison
<
tYPE
>
=
<
Cm.P
>
See also section 3.6.5.
Mnem-
onic
Meaning
Adjustable Range
Default
setting
Customer
setting
tArE
Performs automatic ‘Tare’ correction.
See ’USER CALIBRATION’ section for further
description
OFF
= Off
on
= Start correction
busy
= Calculating value
OFF
CAL.P
Calibration password.
See ‘USER CALIBRATION’
0
to
99999
3
The following four parameters only appear when the correct password has been entered
CAL
Calibration type
Fact
Factory calibration
restored
FAct
USEr
User calibration enabled
The following three parameters are only shown if
<
USEr
>
is selected as the calibration type
Pnt.L
Start point low calibration
OFF
Calibration complete
OFF
on
Start low point calibration
Pnt.H
Start point high calibration
OFF
Calibration complete
OFF
on
Start high point
calibration
tArE.v
Tare Value
This allows a fixed offset to
be applied to the displayed
reading. It must be set
before auto tare is started
-999.9
to
99999
display units
0.0
S.G
Specific
gravity
multiplier
For materials with specific
gravity different from water
(1)
0.01
to
999.9
1.00
ScL.L
Scale Low
point
Automatically adjusts to the
value entered at
<
Pnt.L
>
-999.9
to
99999
display units
ScL.H
Scale High
point
Automatically adjusts to the
value entered at
<
Pnt.H
>
-999.9
to
99999
display units
Calibration Type = Manual
<
tYPE
>
=
<
mAn
>
See also section 3.6.7.
Mnem-
onic
Meaning
Adjustable Range
Default
setting
Customer
setting
CAL.P
Calibration password -See ‘USER
CALIBRATION’
0
to
99999
3
The following four parameters only appear when the correct password has been entered
CAL
Calibration type
Fact
Factory calibration
restored
FAct
USEr
User calibration enabled
The following three parameters are only shown if
<
USEr
> is selected as the calibration type
inP.L
Input low
Set to the low electrical input
which is to correspond to the
low display reading
-999.9
to
99999
display units
ScL.L
Scale Low
point
Set to the display reading
corresponding to
<
inP.L
>
-999.9
to
99999
display units
0
inP.H
Input high
Set to the high electrical input
which is to correspond to the
high display reading
-999.9
to
99999
display units
ScL.H
Scale High
point
Set to the display reading
which corresponds
to
<
inP.H
>
-999.9
to
99999
display units
0
CAL1
CAL2
or
CAL1
CAL2
or
22