background image

Issue 2,   Nov-98.  Applies to software versions 1.3 & 1.4                           -7-                                                                                         HA026270

..........Timer Operating Modes continued

 - Mode 3, Time from Cold and Switch Off

This is the same as mode 1 except that the timer will start counting
down immediately without waiting for the temperature to reach
setpoint.

 Mode 4, Time from Cold No Switch Off

This is the same as mode 2 except that the timer will start counting
down without waiting for the controller to reach setpoint.

 Mode 5, Delayed Switch On

This mode applies a time delay before turning on the heating (or
cooling).  When the timer is started, the controller will always
switch to standby mode and start counting down.  When the timer
has timed out, the controller will switch into automatic control,
apply heating (or cooling) and control indefinitely at the setpoint.

To Program a Ramp-Dwell profile
A simple ramp-dwell profile can be programmed using 

 

(setpoint rate limit) in combination with the timer.  To use this
feature, first reveal 

  and   (the working setpoint) using

the method described in “To Hide, Reveal and Promote”
parameters.  

  will then appear in the HOME list.

Set 

  to the required ramp rate  It is adjustable in 1/10

th

 of

the least significant display units per minute.  That is if the display
is configured 0 to 1000

o

C, setpoint rate limit can be adjusted

between 0.1 and 999.9 

o

C per minute.

When setpoint rate limit has been enabled and the timer is started,
the working setpoint, 

, will first step to the measured

temperature and then ramp at the setpoint rate limit, 

, to the

target setpoint.
In modes 1 and 2 timing will start when the measured temperature
is within 1

o

C of the target setpoint.  In modes 3 and 4 it will start

when 

 is within 1

o

C of the target setpoint.

T

S

TART 

A

ND 

R

ESET 

T

HE 

T

IMER

There are two methods:

Method 1.
This is the simplest method to control the timer.

• 

Press 

 until you reach the 

  list

• 

Press 

 until you reach the 

 parameter (time

remaining).

TIP:  Promote 

 to the HOME list for quick access, as

described in ‘To Hide, Revealing and Promote Parameters.

As soon as a value is entered into 

 timing will commence.

 will count down towards zero.  During the timing period 
can be increased or decreased according to the demands of the
process.  Setting the value to zero will end the timing period.

When 

 reaches zero. ‘’ will flash in the main display.

The timer will remain indefinitely in this state until a new value is
entered, when the timer will restart.
To reset the timer, press         and  

  together.  ‘

’ will stop

flashing .
To restart the timer, enter a new value into 

Method 2.
Use this method if you want to set a fixed time and use the 

parameter to start and stop the timer.

The 

 parameter can also be switched between  and

 by configuring the logic I/O as a Off/run contact closure
input.
Open the external contact to select 

.  This is an edge triggered

action.  Close the contact to select 

.   is forced whenever

the contact is closed.

Press   

   or  

   to enter the

required timing period in minutes.
(0 to 9999).

Press         to return to the HOME display

 

Press  

  to reach the 

 List

heading.

Press until you reach 

Dwell time

Press 

  or 

  to enter a

timing period in minutes
(0-9999).

Timer Status
To start the timer, press 

 or 

to select 

 

.

The dwell time will be loaded into

 and timing will commence.

To reset the timer, select 

.

The time remaining 

 will be set

to 

.

Press 

 and 

 together to return to the HOME display.

Standby mode

Temperature

Setpoint

Reset

Timing

End

 

 flashes

Temperature

Setpoint

Reset

Timing

End

 

 flashes

Indefinite dwell at

setpoint

Indefinite dwell at

setpoint

Temperature

Setpoint

Reset

Timing

Reset

Summary of Contents for 2116

Page 1: ...e latching ears click back into place to maintain the IP65 sealing Output ratings Logic Output 9Vdc 12mA non isolated from sensor input Used for Heating Cooling or Alarm Relay Output 2A 264V ac resistive Used for Heating Cooling or Alarm Contact Closure Input replaces Logic Output Used for Alarm Acknowledge or Timer start reset Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16...

Page 2: ... TO ADJUST THE REQUIRED TEMPERATURE SETPOINT Press and release quickly the or button The setpoint will be displayed for 2 seconds TO VIEW THE DISPLAY UNITS Press and release quickly the or button The display units will be flashed for 0 5 sec If you get lost pressing and together will always return you to the HOME display If at any time no key is pressed within 45 seconds the display will always re...

Page 3: ...ge setpoint limits and access the in built timer Change input and output limits TO ADJUST THE ALARM SETPOINTS TRIP LEVELS Alarm setpoints are found under the list Press twice to choose the list Note The other parameters listed on pages 4 and 5 are accessed and adjusted in exactly the same way as this example Keep pressing to select more list headings eventually returning to the HOME display This i...

Page 4: ...larm type setpoint limits Alarm 3 Setpoint Full Scale Low Full Scale High Deviation Deviation High Deviation Low Alarm Hysteresis to in display units This value is common to all alarms Hysterisis is used to prevent the alarm output chattering by setting a difference between the alarm switch ON and switch OFF points Loop Break Time to minutes Home List Alarm List Autotune List PID 2 List Setpoint L...

Page 5: ...o seconds Cold Junction Temperature measured at rear terminals Read only Millivolt Input measured at the rear terminals Read only Process value Offset to display units Calibration Password to User Calibration Enable Re instates factory calibration Re instates user calibration Low Calibration Point to display units Low Point Calibration Offset to display units High Calibration Point to display unit...

Page 6: ...ill switch to standby mode The MAN beacon will light and will be flashed in the main display The process will cool down The timer will remain indefinitely in this state until reset When Reset will stop flashing The controller will return to reset in standby mode It can be returned to automatic control by setting the parameter in the HOME list to Mode 2 Dwell No Switch Off High alarm 2 has been sel...

Page 7: ...art when is within 1 o C of the target setpoint TO START AND RESET THE TIMER There are two methods Method 1 This is the simplest method to control the timer Press until you reach the list Press until you reach the parameter time remaining TIP Promote to the HOME list for quick access as described in To Hide Revealing and Promote Parameters As soon as a value is entered into timing will commence wi...

Page 8: ...larm Configuration The list configures the three internal soft alarms and causes the appropriate alarm message to be flashed in the HOME display At this stage the alarm is indication only known as a soft alarm To make the alarms operate the relay or logic outputs follow the instructions under Relay and Logic input output Configuration Alarm Type Meaning Alarm 1 The alarm is disabled Full Scale Low...

Page 9: ...ions can be added to the relay or logic output by repeating steps 4 5 and 6 above Two decimal points will appear in those functions that has been added to the output Continued in the next column To Clear Alarms from an Output 1 Press until to reach 2 Press or to select 3 Leave for 2 seconds The display returns to which disconnects all alarms from the relay Passwords Passwords Range Default Full an...

Page 10: ...ons together to return to the HOME display The display will flash to indicate that tuning is in progress 4 The controller will induce an oscillation in the temperature by turning the heating on and then off 5 After two cycles of oscillation the tuning will be completed and the tuner will switch itself off 6 The controller will then calculate the tuning parameters and resume normal control action I...

Page 11: ...n these instructions is subject to change without notice While every effort has been made to ensure the accuracy of the information Eurotherm Controls shall not be held liable for errors contained herein Unpacking and storage The packaging should contain the controller with two panel retaining clips and this instruction leaflet If the packaging or the controller are damaged do not install the prod...

Page 12: ...oming detached from the process thermocouple wiring becoming short circuit the controller failing with its heating output constantly on an external valve or contactor sticking in the heating condition Where damage or injury is possible we recommend fitting a separate over temperature protection unit with an independent temperature sensor which will isolate the heating circuit Please note that the ...

Page 13: ...Issue 2 Nov 98 Applies to software versions 1 3 1 4 13 HA026270 ...

Reviews: