background image

Issue 2,      Nov-98      Applies to software versions 1.3 & 1.4                       -4-                                                                                           HA026270

PARAMETER LISTS

Parameter Tables

Home List

Adjustable Range

Default setting

Customer setting

Output Power demand in %

-100 = max cooling,  100.0 = max heating.

Working Setpoint

Only appears when setpoint rate limit enabled

Read only

Read only

 

Manual/Auto Select


Automatic control selected

Manual standby selected

Home Display Options




Standard - Shows the process value with the

setpoint accessed by pressing the 

 and 

buttons.

Displays the output power - for use as a manual
station.  (Only applies to software version 1.4)

Blank Display (only alarm messages flashed)

Displays the Process Value only

Displays the  Alarm 2 Setpoint only

Displays the Process Value with Alarm 2

Setpoint accessed by the 

 and 

  buttons

Alarm List (See page 3)

Adjustable Range

Default Setting

Customer setting

   

Alarm 1 Setpoint

In place of dashes, the last three

Between low and high

   

Alarm 2 Setpoint

letters indicate the alarm type:

setpoint limits

   

Alarm 3 Setpoint

 

Full Scale Low

 

Full Scale High

 

Deviation

 

Deviation High

 

Deviation Low

Alarm Hysteresis

to

 in display units (This value is common to all

alarms)  Hysterisis is used to prevent the alarm output
‘chattering’ by setting a difference between the alarm switch
ON and switch OFF points

 

Loop Break Time

to

 minutes

 

 

  

  

 

 

 

 

Home

List

Alarm

List

Autotune

List

PID

(2)

 List

Setpoint

List

Input

List

Output

List

On/Off

(2)

List

Access

List

Shaded boxes are hidden when shipped from the factory.
To reveal see ‘’To Hide, Reveal and Promote Parameters” on page 6.

 

 

(1)

(1)

(1)



 

 

 

!

  

 


"

#$

 

Summary

1. Press    to step across the list headings.

2. Press    to step down the parameters

within a particular list.  You will eventually
return to the list heading.

3. Press 

 

 to view the value of a selected

parameter.  Keep pressing to decrease the
value.

4. Press   to view the value of a selected

parameter.  Keep pressing to increase the
value.

X2

Notes:
1. 

In place of dashes, the last three letters
depend on the alarm type.  See “Adjusting
the alarm setpoints” on page 3.

2. 

Either the PID list or the On/Off list will be
present depending upon the configuration
of the controller.

X2

Summary of Contents for 2116

Page 1: ...e latching ears click back into place to maintain the IP65 sealing Output ratings Logic Output 9Vdc 12mA non isolated from sensor input Used for Heating Cooling or Alarm Relay Output 2A 264V ac resistive Used for Heating Cooling or Alarm Contact Closure Input replaces Logic Output Used for Alarm Acknowledge or Timer start reset Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16...

Page 2: ... TO ADJUST THE REQUIRED TEMPERATURE SETPOINT Press and release quickly the or button The setpoint will be displayed for 2 seconds TO VIEW THE DISPLAY UNITS Press and release quickly the or button The display units will be flashed for 0 5 sec If you get lost pressing and together will always return you to the HOME display If at any time no key is pressed within 45 seconds the display will always re...

Page 3: ...ge setpoint limits and access the in built timer Change input and output limits TO ADJUST THE ALARM SETPOINTS TRIP LEVELS Alarm setpoints are found under the list Press twice to choose the list Note The other parameters listed on pages 4 and 5 are accessed and adjusted in exactly the same way as this example Keep pressing to select more list headings eventually returning to the HOME display This i...

Page 4: ...larm type setpoint limits Alarm 3 Setpoint Full Scale Low Full Scale High Deviation Deviation High Deviation Low Alarm Hysteresis to in display units This value is common to all alarms Hysterisis is used to prevent the alarm output chattering by setting a difference between the alarm switch ON and switch OFF points Loop Break Time to minutes Home List Alarm List Autotune List PID 2 List Setpoint L...

Page 5: ...o seconds Cold Junction Temperature measured at rear terminals Read only Millivolt Input measured at the rear terminals Read only Process value Offset to display units Calibration Password to User Calibration Enable Re instates factory calibration Re instates user calibration Low Calibration Point to display units Low Point Calibration Offset to display units High Calibration Point to display unit...

Page 6: ...ill switch to standby mode The MAN beacon will light and will be flashed in the main display The process will cool down The timer will remain indefinitely in this state until reset When Reset will stop flashing The controller will return to reset in standby mode It can be returned to automatic control by setting the parameter in the HOME list to Mode 2 Dwell No Switch Off High alarm 2 has been sel...

Page 7: ...art when is within 1 o C of the target setpoint TO START AND RESET THE TIMER There are two methods Method 1 This is the simplest method to control the timer Press until you reach the list Press until you reach the parameter time remaining TIP Promote to the HOME list for quick access as described in To Hide Revealing and Promote Parameters As soon as a value is entered into timing will commence wi...

Page 8: ...larm Configuration The list configures the three internal soft alarms and causes the appropriate alarm message to be flashed in the HOME display At this stage the alarm is indication only known as a soft alarm To make the alarms operate the relay or logic outputs follow the instructions under Relay and Logic input output Configuration Alarm Type Meaning Alarm 1 The alarm is disabled Full Scale Low...

Page 9: ...ions can be added to the relay or logic output by repeating steps 4 5 and 6 above Two decimal points will appear in those functions that has been added to the output Continued in the next column To Clear Alarms from an Output 1 Press until to reach 2 Press or to select 3 Leave for 2 seconds The display returns to which disconnects all alarms from the relay Passwords Passwords Range Default Full an...

Page 10: ...ons together to return to the HOME display The display will flash to indicate that tuning is in progress 4 The controller will induce an oscillation in the temperature by turning the heating on and then off 5 After two cycles of oscillation the tuning will be completed and the tuner will switch itself off 6 The controller will then calculate the tuning parameters and resume normal control action I...

Page 11: ...n these instructions is subject to change without notice While every effort has been made to ensure the accuracy of the information Eurotherm Controls shall not be held liable for errors contained herein Unpacking and storage The packaging should contain the controller with two panel retaining clips and this instruction leaflet If the packaging or the controller are damaged do not install the prod...

Page 12: ...oming detached from the process thermocouple wiring becoming short circuit the controller failing with its heating output constantly on an external valve or contactor sticking in the heating condition Where damage or injury is possible we recommend fitting a separate over temperature protection unit with an independent temperature sensor which will isolate the heating circuit Please note that the ...

Page 13: ...Issue 2 Nov 98 Applies to software versions 1 3 1 4 13 HA026270 ...

Reviews: