Issue 2, Nov-98.  Applies to software versions 1.3 & 1.4

-1-

 

      HA026270

2132 and 2116  

PID

 

Temperature Controllers

Installing and Operating Instructions

Thank you for choosing the 2132 or 2116 Temperature Controller.
Supplied in 1/32 and 1/16 DIN panel sizes they are designed for
accurate, stable control of ovens, chillers, sterilisers and other
heating and cooling processes. Two outputs are configurable for
heating, cooling and alarms.

D

IMENSIONS AND 

I

NSTALLATION

Model 2132

Model 2116

E

LECTRICAL 

C

ONNECTIONS

The controller is supplied configured according to the order code
given on page 11.  Check this on the side labels to determine the
configuration of your particular controller.

To Install the Controller

Please read the safety information on pages 11 & 12 before
proceeding.
1.  Prepare the panel cut-out to the size shown
2.  Insert the controller through the cut-out.
3.  Spring the panel retaining clips into place.  Secure the

controller in position by holding it level and pushing both
retaining clips forward.

4.  Peel off the protective cover from the display

Unplugging the Controller

The controller can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging it back into its sleeve, ensure that the latching ears
click back into place to maintain the IP65 sealing.

Output ratings

Logic Output:  9Vdc,  12mA (non-isolated from sensor input).
Used for:  Heating, Cooling or Alarm.

Relay Output:  2A,  264V ac resistive.
Used for:  Heating, Cooling or Alarm.

Contact Closure Input (replaces Logic Output).
Used for:  Alarm Acknowledge or Timer start/reset

Wire Sizes

The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to
22AWG).  Hinged covers prevent hands or metal making
accidental contact with live wires.  The rear terminal screws
should be tightened to 0.4Nm (3.5lb in).

Panel cut-out

24mm

(0.95in)

48mm  (1.89in)

103mm  (4.01in)

mm

22.22  

-0.0, +0.3

x 45    

-0.0,  +0.6

Inch

0.88    

-0.0, +0.10

x 1.77 

-0.0, +0.02

Latching ears

Panel retaining clips

Recommended minimum
spacing of controllers in
both sizes

10mm

(0.4 in)

38mm

(1.5 in)

(Not to
scale)

45 x 45 mm

             -0.0, + 0.6

1.77 x 1.77in

            -0.00, +0.02

103mm  (4.01in)

Latching ears

Panel retaining clips

48mm

(1.89in)

Panel cut-out

48mm  (1.89in)

1B

1A

Pt100

T/C

Output 2

Relay

Neutral

Line

Logic

I/O

Model 2132

External Relay Module
(Operated by the logic output)

OR

Solid
State
Relay
(SSR)

2.49 

Sensor Inputs

AB

V+

V-

AA

L

N

+

-

mA

Low voltage supply

24

24

20-29 Vac/dc

85-264Vac

1B

1A

External Relay Module
(Operated by the logic output)

Model 2116

OR

Solid
State
Relay
(SSR)

+

-

Logic

I/O

Line

Neutral

Output 2

Relay

T/C Pt100 mA

Sensor Inputs

20-29V ac/dc

 Low voltage

 supply

L

N

AA

AB

V+

V-

 24

 24

1A

1B

2.49 

85-264Vac

This controller meets the European Directives on safety and
EMC.

Summary of Contents for 2116

Page 1: ...e latching ears click back into place to maintain the IP65 sealing Output ratings Logic Output 9Vdc 12mA non isolated from sensor input Used for Heating Cooling or Alarm Relay Output 2A 264V ac resistive Used for Heating Cooling or Alarm Contact Closure Input replaces Logic Output Used for Alarm Acknowledge or Timer start reset Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16...

Page 2: ... TO ADJUST THE REQUIRED TEMPERATURE SETPOINT Press and release quickly the or button The setpoint will be displayed for 2 seconds TO VIEW THE DISPLAY UNITS Press and release quickly the or button The display units will be flashed for 0 5 sec If you get lost pressing and together will always return you to the HOME display If at any time no key is pressed within 45 seconds the display will always re...

Page 3: ...ge setpoint limits and access the in built timer Change input and output limits TO ADJUST THE ALARM SETPOINTS TRIP LEVELS Alarm setpoints are found under the list Press twice to choose the list Note The other parameters listed on pages 4 and 5 are accessed and adjusted in exactly the same way as this example Keep pressing to select more list headings eventually returning to the HOME display This i...

Page 4: ...larm type setpoint limits Alarm 3 Setpoint Full Scale Low Full Scale High Deviation Deviation High Deviation Low Alarm Hysteresis to in display units This value is common to all alarms Hysterisis is used to prevent the alarm output chattering by setting a difference between the alarm switch ON and switch OFF points Loop Break Time to minutes Home List Alarm List Autotune List PID 2 List Setpoint L...

Page 5: ...o seconds Cold Junction Temperature measured at rear terminals Read only Millivolt Input measured at the rear terminals Read only Process value Offset to display units Calibration Password to User Calibration Enable Re instates factory calibration Re instates user calibration Low Calibration Point to display units Low Point Calibration Offset to display units High Calibration Point to display unit...

Page 6: ...ill switch to standby mode The MAN beacon will light and will be flashed in the main display The process will cool down The timer will remain indefinitely in this state until reset When Reset will stop flashing The controller will return to reset in standby mode It can be returned to automatic control by setting the parameter in the HOME list to Mode 2 Dwell No Switch Off High alarm 2 has been sel...

Page 7: ...art when is within 1 o C of the target setpoint TO START AND RESET THE TIMER There are two methods Method 1 This is the simplest method to control the timer Press until you reach the list Press until you reach the parameter time remaining TIP Promote to the HOME list for quick access as described in To Hide Revealing and Promote Parameters As soon as a value is entered into timing will commence wi...

Page 8: ...larm Configuration The list configures the three internal soft alarms and causes the appropriate alarm message to be flashed in the HOME display At this stage the alarm is indication only known as a soft alarm To make the alarms operate the relay or logic outputs follow the instructions under Relay and Logic input output Configuration Alarm Type Meaning Alarm 1 The alarm is disabled Full Scale Low...

Page 9: ...ions can be added to the relay or logic output by repeating steps 4 5 and 6 above Two decimal points will appear in those functions that has been added to the output Continued in the next column To Clear Alarms from an Output 1 Press until to reach 2 Press or to select 3 Leave for 2 seconds The display returns to which disconnects all alarms from the relay Passwords Passwords Range Default Full an...

Page 10: ...ons together to return to the HOME display The display will flash to indicate that tuning is in progress 4 The controller will induce an oscillation in the temperature by turning the heating on and then off 5 After two cycles of oscillation the tuning will be completed and the tuner will switch itself off 6 The controller will then calculate the tuning parameters and resume normal control action I...

Page 11: ...n these instructions is subject to change without notice While every effort has been made to ensure the accuracy of the information Eurotherm Controls shall not be held liable for errors contained herein Unpacking and storage The packaging should contain the controller with two panel retaining clips and this instruction leaflet If the packaging or the controller are damaged do not install the prod...

Page 12: ...oming detached from the process thermocouple wiring becoming short circuit the controller failing with its heating output constantly on an external valve or contactor sticking in the heating condition Where damage or injury is possible we recommend fitting a separate over temperature protection unit with an independent temperature sensor which will isolate the heating circuit Please note that the ...

Page 13: ...Issue 2 Nov 98 Applies to software versions 1 3 1 4 13 HA026270 ...

Reviews: