26
JVF-M2 Series Outdoor Gas Fireplace
IGM2S-190417
INDEX
LP (PROPANE) CONVERSION
Applicable Models:
JVF-60-M2-S
JVF-60-M2-ST
WARNING
This conversion kit shall be installed by a qualified service
agency in accordance with the manufacturer’s instructions
and all applicable codes and requirements of the Authority
having jurisdiction. If the information in these instructions is
not followed exactly, a fire, explosion or production of carbon
monoxide may result causing property damage, personal injury
or loss of life. The qualified service agency is responsible for
the proper installation of this kit. The installation is not proper
and complete until the operation of the converted appliance
is checked as specified in the manufacturer’s instructions
supplied with the kit.
This kit is to be used to convert the J-M2 models from natural gas to propane.
It is not to be used to convert any other
models.
The conversion must be performed only by a qualified service person or agency.
If the fireplace or burner has been connected to natural gas, contact your local gas supplier to have the natural gas
supply disconnected and removed.
The maximum and minimum inlet supply pressure is controlled by the regulator. It is set at a supply pressure of 11
inches water column.
The manifold pressure cannot be adjusted. It should be 10.3 inches water column. The propane input is rated at 65,000
Btu/hr.
For installations above 2000 feet elevation, check with local authorities or your propane supplier for proper deration.
Please refer to page 14 for LP cylinder enclosure.
The
JVF-SA-LPCK-OZ
kit contains the following items: