Error out 14-16
The
connection
is
named
"ERROR
OUT
(MAX
1A)"
on
the
adhesive
sticker.
The
output
is
potential
‐
free
and
has
both
an
NC
and
an
NO
connection.
It
can
be
used
to
get
a
signal
to
an
external
unit
or
to
a
GSM
unit.
The
output
can
be
loaded
with
max
1A
During
normal
operations
with
no
alarm,
there
is
contact
between
terminals
15
and
16.
In
the
event
of
an
alarm
or
power
failure
there
is
contact
between
14
and
15
Error
or
power
failure
(NC)
Normal
operations
(NO)
Digital input 17-18
Connection
named
"EXTRA
DIGITAL
IN"
on
the
adhesive
sticker.
The
input
should
be
potential
‐
free
and
has
different
functions
depending
on
what
settings
are
chosen
in
the
display.
From
program
version
1.4
the
set
function
is
standby.
If
the
input
is
closed
the
heat
pump
and
electric
heater
will
be
blocked
until
the
input
is
opened
again.
When
closing
the
input
below
display
text
will
be
activated.
****SYSTEM OK*****
Standby mode active
Heatpump/El.heater
blocked. Time 26min