Sensors
EUROMAG | SENSORS | Ed. 04/2019
5.2
ELECTRICAL DIAGRAMS
5.2.1 Connection with standard single-shielded electrode cable
The shields must ONLY be connected on the converter side.
A
B
T
C
D
E
F
A
B
T
C
D
E
F
Coils cable
Electrodes cable
Separation box of the sensor
Converter
Fig. 52 Standard single-shielded cables - C022
5.2.2 Connection with standard double-shielded electrode cable
The shield of the coil cable must be connected ONLY on the converter side, as well as the INTERNAL
shield of the electrode cable. The EXTERNAL shield of the electrode cable must be connected to the
case on the earthing point of the separation box of the sensor.
A
B
T
C
D
E
F
A
B
T
C
D
E
F
Coils cable
Electrodes cable
Separation box of the sensor
Converter
Fig. 53 Standard single-shielded cables - C028