13) Parameter group 600: DC-Brake control / Aux. functions
13) Parameter group 600: DC-Bake control / Aux. functions
DC-Brake function parameters:
F600
DC-Brake function
activation
Selection: 0: DC-Brake deactivated
1: DC injection before START
2: DC injection after STOP
3: Before START and after STOP
Default setting 0
F601
Frequency threshold for
DC-injection
Range: 0.2…5.0 Hz
Default setting 1.00 Hz
F602
Intensity DC-Brake START
F603
Intensity DC-Brake STOP
Range: 0…100%
Default setting 10
F604
DC-Brake duration START
F605
DC-Brake duration STOP
Range: 0.0 - 10.0 sec.
Default setting 0.5 sec.
F606
DC- Brake mode
Selection: 0=Voltage controlled
1=Current controlled
2=Auto-Voltage controlled
Default setting 0
Parameter for DC-Brake control:
Attention!! Improperly programmed DC-Brake function may result in inverter overcurrent
trip and/or motor overheating
DC-Brake active optional signalized through digital output – function assignation:
6
Current- Voltage limiting functions
Limiting functions for current and voltage are available in standard E800 inverters
Current limiting function: This function allow to program a motor current threshold. If motor current reaches the
threshold (F608) during acceleration, the acceleration ramp will hold on, until current drops below the limit.
If current exceed the limit at target frequency (ramp completed), the frequency will be reduced, if necessary, down to
the minimum frequency.
Current limiting function is always deactivated during deceleration ramp.
Voltage limiting function: To limit the DC-link voltage increase, due to energy regeneration during deceleration phase.
If voltage reaches the limit (F609), the limiting function will stretch the deceleration ramp.
The limiting status of the inverter can be signalized through any programmable digital output. Function assignation
code:
12
F607
Activation of both limiting functions
Selection: 0: activated
1: deactivated
Default setting: 0
F608
Current limit (% rated current)
Range: 60…200 %
Default setting: 160 %
F609
DC voltage limit (% rated voltage)
Range: 60…200 %
Default setting: 140 %
F610
Max. duration if limiting status (sec.)
Bereich: 0.1…3000.0 sec.
Default setting: 5.0 sec.
If limiting status of the inverter takes longer than the time, set in
F610
, the system will stop, and
OL1
will appear on the
display.
t
V
/
A
F604
Hz
F
605
t
F601
F602
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
- 52 -