10) Parametergruppe 300: Digital I/O Konfiguration
E800 – Rev.01 -D- SOFT Rev. 2.04
© 2015 EURADRIVES EURDIE GmbH
- 46 -
Fixed-frequencies selection – table 300-1
K4
6
K3
5
K2
4
K1
3
Frequency Programming
parameter
0 0 0 0
0 0 0
1 Fixed-frequency
1
F504/F519/F534/F549/F557/F565
0 0
1
0
Fixed-frequency 2
F505/F520/F535/F550/F558/F566
0 0 1 1
Fixed-frequency
3
F506/F521/F536/F551/F559/F567
0
1
0 0
Fixed-frequency 4
F507/F522/F537/F552/F560/F568
0 1 0 1
Fixed-frequency
5
F508/F523/F538/F553/F561/F569
0 1 1 0
Fixed-frequency
6
F509/F524/F539/F554/F562/F570
0 1 1 1
Fixed-frequency
7
F510/F525/F540/F555/F563/F571
1
0 0 0
Fixed-frequency 8
F511/F526/F541/F556/F564/F572
1 0 0 1
Fixed-frequency
9
F512/F527/F542/F573
1 0 1 0
Fixed-frequency
10
F513/F528/F543/F574
1 0 1 1
Fixed-frequency
11
F514/F529/F544/F575
1 1 0 0
Fixed-frequency
12
F515/F530/F545/F576
1 1 0 1
Fixed-frequency
13
F516/F531/F546/F577
1 1 1 0
Fixed-frequency
14
F517/F532/F547/F578
1 1 1 1
Fixed-frequency
15
F518/F533/F548/F579
Please note: If F500=1, binary selection K1...K4 – for direct selection via K1...K4, use fixed-frequency 1, 2, 4 and 8
If (F500=0) K1...K3 may be used for direct selection of 3 fixed frequencies
Accel./Decel. ramp selection - table 300-2
BIT1
Function assignation
18
BIT2
Function assignation
34
Accel./Decel.
Ramp-set
Programming
parameter
1 0
Ramp set 1
F114 / F115
0 0
Ramp set 2
F116 / F117
1 1
Ramp set 3
F277 / F278
0 1
Ramp set 4
F279 / F280
F324
"STOP - DISABLE" logic selection
(8)
Default setting 0
F325
"EMERGENCY -STOP EXTERN" logic
(9)
Selection: 0=LOW active (NPN)
1=HIGH active (PNP)
Default setting 0
F326
Watchdiog delay time
Range: 0,1…30.000 sec.
Default setting10,0 sec
F327
Watchdog STOP mode
Selection: 0=free STOP
1=ramp STOP
Default setting 0
F328
Digital input filter factor
Range: 1…100
Default setting 10
IF 326=0: The watchdog function is deactivated. Watchdog function can only work, if one digital input is mapped
as watchdog pulse input
(53)