10) Parametergruppe 300: Digital I/O Konfiguration
Function mapping for digital input channels
DI1 – DI5(8)
F316
Function assignation to DI1
Default setting
11
(JOG-forward)
F317
Function assignation to DI2
Default setting
9
(EMERGENCY-STOP EXT.)
F318
Function assignation to DI3
Default setting
15
(TERMINAL "FORWARD")
F319
Function assignation to DI4
Default setting
16
(TERMINAL "REVERSE")
F320
Function assignation to DI5
Default setting
7
(RESET)
F321
Function assignation to DI6
Default setting
8
(STOP-DISABLE)
F322
Function assignation to DI7
Default setting
1
(START)
F323
Function assignation to DI8
Function mapping:
0….53
Default setting
2
(STOP)
Attention:
One function can be assigned to one single digital input only (no multiple inputs) If a function is already assigned to a
certain input (factory set), this assignment must be deleted (set assignment to 0), before assigning to another input.
Table of digital input functions
VALUE Function
Description
0
No function
No function assigned, for unused inputs
1
START function
The input starts the drive system – same as
"RUN"
on keypad
2
STOP function
Input stops the system – same as
"STOP"
on keypad
3
Fix-frequency K1
4
Fix-frequency K2
5
Fix-frequency K3
6
Fix-frequency K4
15-Fix-programmed frequencies are selectable
(see table below 300-1)
7
RESET
General reset, error reset – same as
"STOP/RESET"
on keypad
8
STOP-DISABLE "Free
STOP"
system stops with inertia (logical inversion:
F324
)
9
EMERGENCY STOP
Ext. Emerg. STOP signal,
ESP
on display (signal logic:
F325
)
10
RAMPSTOP
Inverter holds the actual frequency, independent from other signals (except STOP
signal) – ramps are stopped
11
JOG foreward
12
JOG reverse
JOG control, see
F124, F125
and
F126
for parametrizing
13
Motorpotenti
14
Motorpotentiometer -
Motorpotentiometer-function, to increase/decrease frequency, (with internal speed
reference
F203=0 / 5
, control parameter:
F113, F210, F211
).
15
Terminal “FWD”
16
Terminal “REV”
17
Terminal “X”
Assignation of terminal function
"FWD", "REV",
and
"X"
(see two/three wire control –
parameter
F208
)
18
BIT1 Ramp set selection
Selection of Acce./Decel. ramp set
(BIT1)
– (see
table 300-2)
19
Reserved
--
20
Reserved
21
Reference source
Selection of different speed reference sources - combinations (see
F207
)
22-31
Reserved
32
FIRE pressure
To select "Fire Mode" pressure setpoint (parameter
FA58
).
33
FIRE MODE
Activation of the "FIRE MODE"
(FA59)
34
BIT2 Ramp set selection
Selection of Accel. / Decel. ramp set
(BIT2)
– (see
table 300-2)
37
NTC / NO
Motor heath monitoring via
NTC
/
NO
contact (KLIXON)
38
PTC / NC
Motor heath monitoring via
PTC
/
NC
contact (KLIXON)
53
Watchdog
Watchdog control-pulse input
E800 – Rev.01 -D- SOFT Rev. 2.04