16. System status table, module LEDs
All diagnostic messages are listed below. The scope of the possible messages may differ depending on the type and number
of modules/submodules used.
16.1. System indications if there are faults (module LEDs)
If there are faults, the bit
LM.E_G
is set. After the fault has been rectified, it can be acknowledged using the bit
LM.ACK_G
.
The bit
LM.E_G
is reset during this process. Exception: escape release fault (see
19.2. Fault on actuating the escape
release on page 38
)
Operating mode
LED indicator
Device diagnostics r
elated fault/status bit
State
POWER (gn)
ST
ATE (gn)
Lock (ye), only MGB2-L1/-L2
DIA (r
d)
Fault display
1 x
LM.E_G
Handle module teach-in fault (e.g. teach-in operation interrupt-
ed too early), configuration teach-in fault
3 x
LM.E_G
Handle module read fault (e.g. fault in code or code cannot
be read)**
5 x
LM.E_G
Environment fault, disabled actuator, power supply outside the
permissible range
LM.E_G
Internal fault (e.g. component faulty, data error)*
1 x
LM.E_ER
Plausibility fault, signal sequence incorrect,
e.g. broken bolt tongue recognized ***
or after actuation of the escape release, for example*
1 x
BM.E_MLI
MLI communication fault (indication on bus module)
Key to symbols
LED not illuminated
LED illuminated
10 Hz, 8 s
LED flashes for 8 seconds at 10 Hz
3 x
LED flashes three times
X
Any state
*
Latching fault; use corresponding output bit
LM.ACK_G
to reset
**
Non-latching fault; open guard and close it again to reset
***
Latching fault; use corresponding output bit
LM.ACK_ER
to reset, door must be open during this process (see chapter
16. System status table, module LEDs on page 33
)
Important
: If you do not find the displayed device status in the System status table, this indicates an internal device fault. In this case, you should contact the manufacturer.