Operating Instructions
Transponder-Coded Safety Switch CTM-L2-AS1B
EN
8. Mounting
CAUTION
Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise
rendered ineffective.
Ì
Observe EN ISO 14119:2013, section 7, for information about reducing the possibilities for by-
passing an interlocking device.
NOTICE
Risk of damage to equipment and malfunctions as a result of incorrect installation.
Ì
Safety switches and actuators must not be used as an end stop.
Ì
Observe EN ISO 14119:2013, sections 5.2 and 5.3, for information about mounting the safety
switch and the actuator.
Ì
Protect the switch against damage, as well as against penetrating foreign objects such as swarf,
sand and blasting shot, etc.
Ì
Observe the min. door radii (see chapter
12.4.1. Dimension drawing for actuator A-B-A1-A1-… on
).
Ì
Observe the maximum permissible angle between switch and actuator (max. 5°).
Ì
Observe the tightening torque for fastening the switch and the actuator (max. 2.9 Nm).
Ì
The rear side of the switch and the actuator’s plate must lie fully on the mounting surface.
Ì
Actuator and safety switch must be mounted such that the actuator is vertically inserted into the
switch when the guard is closed.