2105274-12-08/20 (Translation of the original operating instructions)
Operating instructions
Non-Contact Safety System CES-AZ-UES-…
EN
-Parameter setting operation starts (STATE LED flashes at approx. 1 Hz)
-Wait for acknowledgment of the parameter setting operation (STATE LED goes out after approx. 10 seconds)
5. End parameter setting operation
-Remove jumper between J1 and J2 (for CES-AZ-UES-01B between J and 0V)
-For operating mode
Manual start
: start button must be connected
-For operating mode
with feedback loop
: feedback loop must be connected
-Press reset button or interrupt operating voltage for at least 10 seconds
-Wait for self-test (STATE LED flashes for approx. 10 seconds at 15 Hz)
6. Check all guards for effectiveness
9.2.1. Changing the configuration
The evaluation unit can be re-configured as often as required. For this purpose you must proceed as per the first parameter
setting operation according to the section
9.2. Parameter setting on page 16
.
Faulty actuators can be replaced. The number of parameter setting operations is unlimited.