Operating Instructions

Safety Switch NX…

Correct use

Safety switches series NX are interlocking devices 

without guard locking (type 2). The actuator has 

a low coding level. In combination with a movable 

guard and the machine control, this safety compo-

nent prevents dangerous machine functions from 

occurring while the guard is open. A stop command 

is triggered if the guard is opened during the dan-

gerous machine function.
This means:

 

f

Starting commands that cause a dangerous ma-

chine function must become active only when the 

guard is closed.

 

f

Opening the guard triggers a stop command.

 

f

Closing a guard must not cause automatic starting 

of a dangerous machine function. A separate start 

command must be issued. For exceptions, refer to 

EN ISO 12100 or relevant C-standards.

Before the device is used, a risk assessment must 

be performed on the machine, e.g. in accordance 

with the following standards:

 

f

EN ISO 13849-1

 

f

EN ISO 12100

 

f

IEC 62061

Correct use includes observing the relevant require-

ments for installation and operation, particularly 

based on the following standards:

 

f

EN ISO 13849-1

 

f

EN ISO 14119

 

f

EN 60204-1

Important!

 

f

The user is responsible for the proper integration 

of the device into a safe overall system. For this 

purpose, the overall system must be validated, 

e.g. in accordance with EN ISO 13849-2.

 

f

If the simplified method according to section 6.3 

of EN ISO 13849-1:2015 is used for determining 

the Performance Level (PL), the PL might be re-

duced if several devices are connected in series.

 

f

Logical series connection of safe contacts is 

possible up to PL d in certain circumstances. 

More information about this is available in 

ISO TR 24119.

 

f

If a product data sheet is included with the prod-

uct, the information on the data sheet applies 

in case of discrepancies with the operating 

instructions.

Safety precautions

 WARNING

Danger to life due to improper installation or due 

to bypassing (tampering). Safety components 

perform a personnel protection function.

 

f

Safety components must not be bypassed, 

turned away, removed or otherwise rendered 

ineffective. On this topic pay attention in partic-

ular to the measures for reducing the possibility 

of bypassing according to EN ISO 14119:2013, 

section 7.

 

f

The switching operation must be triggered only 

by actuators designated for this purpose.

 

f

Prevent bypassing by means of replacement 

actuators. For this purpose, restrict access to 

actuators and to keys for releases, for example.

 

f

Mounting, electrical connection and setup only 

by authorized personnel possessing special 

knowledge about handling safety components.

Function

The safety switch monitors the position of movable 

guards. The switching contacts are actuated on the 

insertion/removal of the actuator. 

Switching states

The detailed switching states for your switch can be 

found in Figure 3. All available switching elements 

are described there.

Guard open

The safety contacts   are open.

Guard closed

The safety contacts   are closed.

Selection of the actuator

NOTICE

Damage to the device due to unsuitable actuator. 

Make sure to select the correct actuator (see 

table in Figure 5).
Additionally pay attention to the door radius and 

the mounting options (see Figure 6).

The following versions are available:

 

f

Standard

 actuator with 1 mm insertion depth.

 

f

Overtravel 

actuator with 8 mm insertion depth.

Mounting

NOTICE

Device damage due to improper mounting and 

unsuitable ambient conditions

 

f

Safety switches and actuators must not be used 

as an end stop.

 

f

Observe EN ISO 14119:2013, sections 5.2 and 

5.3, for information about mounting the safety 

switch and the actuator.

 

f

Observe EN  ISO  14119:2013, section 7, for 

information about reducing the possibilities for 

bypassing an interlocking device.

 

f

Protect the switch head against damage, as well 

as penetrating foreign objects such as swarf, 

sand and blasting shot, etc.

 

f

The specified IP degree of protection is applica-

ble only if the housing screws, cable entries and 

plug connectors are properly tightened. Observe 

the tightening torques.

Changing the actuating direction

A

Figure 1:  Changing the actuating direction

1.  Unscrew and open switch cover.
2.  Remove actuating head from the switch by 

turning and refit in the required position (bayo-

net fastening).

3.  Fit the enclosed locking pins for protection 

against twisting (Figure 2). It is then not possi-

ble to change the actuating direction again.

Figure 2:  Fitting the locking pins and the slot cover

4.  Close the switch cover and screw in position.
5.  Cover the unused actuating slot with the en-

closed slot covers.

Electrical connection

 WARNING

Loss of the safety function due to incorrect 

connection.

 

f

Use only safe contacts ( ) for safety functions.

 

f

Strip the insulation from the ends of the individual 

wires over a length of 6

±1 mm

 to ensure a reliable 

contact.

The following information applies to devices 

with cable entry:

1.  Use a suitable tool to open the desired inser-

tion opening.

2.  Fit the cable gland with the appropriate degree 

of protection.

3.  Connect and tighten the terminals with 0.5 Nm 

(for terminal assignment, see Figure 3).

4.  Check that the cable entry is sealed.
5.  Close the switch cover and screw in place 

(tightening torque 0.8 Nm).

Function test

 WARNING

Fatal injury due to faults during the function test.

 

f

Before carrying out the function test, make sure 

that there are no persons in the danger zone.

 

f

Observe the valid accident prevention regula-

tions.

Check the device for correct function after installa-

tion and after every fault.
Proceed as follows:

Mechanical function test

The actuator must slide easily into the actuating 

head. Close the guard several times to check the 

function.

Electrical function test

1.  Switch on operating voltage.
2.  Close all guards.

 

¨

The machine must not start automatically.

3.  Start the machine function.
4.  Open the guard.

 

¨

The machine must switch off and it must not be 

possible to start it as long as the guard is open.

Repeat steps 2 - 4 for each guard.

Summary of Contents for 091682

Page 1: ...ild 3 Dort sind alle verfügbaren Schal telemente beschrieben Schutzeinrichtung geöffnet Die Sicherheitskontakte sind geöffnet Schutzeinrichtung geschlossen Die Sicherheitskontakte sind geschlossen Auswahl des Betätigers HINWEIS Schäden am Gerät durch ungeeigneten Betätiger Achten Sie darauf den richtigen Betätiger auszu wählen siehe Tabelle in Bild 5 Achten Sie dabei auch auf den Türradius und die...

Page 2: ...en von ist eine Kupferleitung für den Temperaturbereich 60 75 C zu verwenden EU Konformitätserklärung Die Konformitätserklärung ist Bestandteil der Be triebsanleitung und liegt dem Gerät als separates Blatt bei Die originale EU Konformitätserklärung finden Sie auch unter www euchner de Service Wenden Sie sich im Servicefall an EUCHNER GmbH Co KG Kohlhammerstraße 16 70771 Leinfelden Echterdingen De...

Page 3: ...X 4 5 42 s s RD GN 51 5 46 58 5 39 19 25 5 160 4 5 21 5 8 5 C B D A Standard D Eintauchtiefe für M5 45 mm ISO 1207 DIN 84 S ISO 4762 DIN 912 NX M M20x1 5 NX N 1 2 NPT Eintauchtiefe Optionales LED Modul Betätiger separat bestellen Betätiger Eintauchtiefe s Standard 32 1 Nachlauf 32 8 Bild 6 Minimale Türradien Betätiger Türradius min mm Betätiger X GQ 300 Betätiger X WQ 300 Radiusbetätiger X LR N 10...

Page 4: ... are described there Guard open The safety contacts are open Guard closed The safety contacts are closed Selection of the actuator NOTICE Damage to the device due to unsuitable actuator Make sure to select the correct actuator see table in Figure 5 Additionally pay attention to the door radius and the mounting options see Figure 6 The following versions are available f Standard actuator with 1 mm ...

Page 5: ...ration of conformity is part of the operating instructions and it is included as a separate sheet with the unit The original EU declaration of conformity can also be found at www euchner com Service If servicing is required please contact EUCHNER GmbH Co KG Kohlhammerstraße 16 70771 Leinfelden Echterdingen Germany Service telephone 49 711 7597 500 E mail support euchner de Internet www euchner com...

Page 6: ...oor open Figure 5 Dimension drawing for NX 4 5 42 s s RD GN 51 5 46 58 5 39 19 25 5 160 4 5 21 5 8 5 C B D A Standard D Insertion depth For M5 45 mm ISO 1207 DIN 84 S ISO 4762 DIN 912 NX M M20x1 5 NX N 1 2 NPT Insertion depth Optional LED module Order actuator separately Actuator Insertion depth s Standard 32 1 Overtravel 32 8 Figure 6 Minimum door radii Actuator Door radius min mm Actuator X GQ 3...

Page 7: ...rotecteur ouvert Les contacts de sécurité sont ouverts Protecteur fermé Les contacts de sécurité sont fermés Choix de l élément d actionnement AVIS Endommagement de l appareil par un élément d actionnement non approprié Veillez à sélection ner l élément d actionnement correct voir tableau de la Figure 5 Tenez compte également du rayon de porte et des possibilités de fixation voir Figure 6 Il exist...

Page 8: ...de conformité fait partie intégrante du mode d emploi et est fournie avec l appareil sur une feuille séparée Vous trouverez aussi la déclaration UE de conformité originale sur le site www euchner com Service Pour toute réparation adressez vous à EUCHNER GmbH Co KG Kohlhammerstraße 16 70771 Leinfelden Echterdingen Allemagne Téléphone du service clientèle 49 711 7597 500 E mail support euchner de In...

Page 9: ... GN 51 5 46 58 5 39 19 25 5 160 4 5 21 5 8 5 C B D A Standard D Profondeur d insertion pour M5 45 mm ISO 1207 DIN 84 S ISO 4762 DIN 912 NX M M20x1 5 NX N 1 2 NPT Profondeur d insertion Module de LED en option Languette à commander séparément Actionneur Prof d insert s Standard 32 1 Surcourse 32 8 Figure 6 Rayons de porte minimum Actionneur Rayon porte min mm Languette X GQ 300 Languette X WQ 300 L...

Page 10: ...igura 3 dove sono descritti tutti i microinterruttori disponibili Riparo aperto I contatti di sicurezza sono aperti Riparo chiuso I contatti di sicurezza sono chiusi Scelta dell azionatore AVVISO Danni al dispositivo causati da un azionatore non idoneo Assicurarsi di scegliere l azionatore corretto vedi tabella alla Figura 5 Tener conto anche del raggio del riparo e delle possibilità di fissaggio ...

Page 11: ...onformità La dichiarazione di conformità è parte integrante delle istruzioni di impiego ed è allegata al dispositivo su un foglio separato La dichiarazione UE di conformità originale si trova anche al sito www euchner com Assistenza Per informazioni e assistenza rivolgersi a EUCHNER GmbH Co KG Kohlhammerstraße 16 70771 Leinfelden Echterdingen Germania Assistenza telefonica 49 711 7597 500 E mail s...

Page 12: ...51 5 46 58 5 39 19 25 5 160 4 5 21 5 8 5 C B D A Standard D Inserimento Per M5 45 mm ISO 1207 DIN 84 S ISO 4762 DIN 912 NX M M20x1 5 NX N 1 2 NPT Inserimento Modulo LED opzionale Gli azionatori vanno ordinati separatamente Azionatore Inserimento s Standard 32 1 Oltrecorsa 32 8 Figura 6 Raggi del riparo minimi Azionatore Raggio riparo min mm Azionatore X GQ 300 Azionatore X WQ 300 Azionatore rotati...

Reviews: