range
exceeded
F < Fmin
–10%
Code: 2.2 V
Description:
fuel level shown is higher than
actual level in tank, the sensor reports an
error at intervals.
Explanation:
the error is encountered when
the sensor is immersed to a depth close to
the maximum, or
–
in case of shorting by
water
–
to any depth. If the error switches to
‘Generator frequency equals
0
’
, it is caused
by the presence of water or impurities in the
fuel.
Cause:
the composition of the liquid
measured differs from that of diesel or
petrol. Periodic shorting of the measuring
element in the tank by water or other
impurities. The sensor has been incorrectly
calibrated.
1.
If the error manifests randomly at
any level of fuel and the error code
switches to 1.4 V (
‘Generator
frequency equals 0’
) from time to
time, follow the instructions for fixing
the error coded by 1.4 V.
2.
If the error manifests at a specific
fuel level, the sensor must be
calibrated. If this does not fix the
problem, contact the manufacturer.