11

®

RDM-31-0222

NORD

canopy

  

 

|

   

OZ 3.0 Installation Guide

5.2  Control Panel and the Ozone Modules data wiring

Three cables are connected to the Control Panel. Data cable (3x0,25mm2) for communication between 

Control Panel and EOZ unit, I/O cable (5x0,5mm2) for connecting to the building automation and LAN cable 

to access the Control Panel via internet.

Ozone Modules are connected sequentially (”daisy-chained”) from the Control Panel to the nearest Ozone 

Module, then to the next module and so on. However, please note that although the physical cabling is 

”chained” from one device to the next, the data cables are connected together in a parallel format. That is, 

similar terminals between devices are connected together; there are no specific ”in” or ”out” data terminals 

on the various components. 
Maximum limit for the number of Ozone Module connected to the Control Panel is 99 and maximum length of 

the data cable is 500m. However, it may be advantageous to have multiple Control Panels in larger facilities. 

Cable bushings come preattached inside the supply chambers.

*3x0,25 mm2 or another shielded data cable with at least 3 conductors.

Data terminal A-, B+ and C (GND) are connected similarly between the Control Panel and each Ozone Module. 

Note the cable colors used on each terminal to ensure all devices are connected similarly.

As stated above, the data cables are typically run through the facility in a daisy-chained format, although the 

individual communications wires themselves are connected in parallel. In this way data communications 

between devices will remain active even in the case one of them is powered off, malfunctioning, or unplugged 

and removed. 

Thus, each A-, B+ and C data wire leading 

in from devices on both sides of any Ozone 

Module in the chain should share the same 

terminal screw in its respective connector. In 

this way the three extra unused terminals just 

below on the connector block can be reserved 

for future expansion. 

Display

Ozone Module 1

PE

L

N

Junction box AP9

Circuit braker

10A fuse 

(max 6 ozonators)

3x0,25 mm²

 

*

3x0,25 mm²

 

*

3x0,25 mm²

 

*

Ozone Module 2

Ozone Module ...

Display

Ozone Module 1

Ozone Module 2

Ozone Module ...

Control Panel

Data cable to 

Ozone Module 1

I/O 

A-

B+

C

C

B+

A-

OUT

IN

Summary of Contents for NORDcanopy OZ 3.0

Page 1: ...NORDcanopy OZ 3 0 Ozone Cleaning System Installation Guide...

Page 2: ...odules 5 3 1 Set the device addresses 5 4 Installation 6 4 1 General information 6 4 2 Connect the pressure measurement hoses 7 4 3 Mount the Control Panel 8 5 Electrical Installation 9 5 1 Connect th...

Page 3: ...t generates ozone O3 Ozone significantly reduces odor grease mold and bacteria ETS NORD AS disclaims any liability in the case that the product is not used in accordance with the manufacturer s instru...

Page 4: ...f Ozone Modules is dependent on the design of the kitchen and the canopy as well as the equipment used for cooking This is decided when planning the kitchen 2 System overview The Ozone Modules produce...

Page 5: ...r intake grid The address is set using the switches marked 1x and 10x The 1x switch is positioned nearest the corner of the circuit board Example Ozone Module one Adress 1 Switch 1x 1 Switch 10x 0 Ozo...

Page 6: ...facturer s drawings The ozone duct must be made of acid resistant stainless steel AISI 316 Before starting the Ozone Module check visually that all ozone duct connections are airtight Always leave a m...

Page 7: ...dule into place securely attach one end of the hose to the hose located in the Ozone Module 100mm flange Raise the module into place gently pulling the hose from its other end to ensure it does not be...

Page 8: ...it near any sources of moisture or heat The housing must be disassembled into three parts Remove the two fixing screws on the sides of the case Before mounting the backplate apply an even strip of wa...

Page 9: ...alarm panel may be connected a single 10A C type slow circuit breaker NOTE Electrical installation must be performed by an authorized electrician and follow local regional and national standards and...

Page 10: ...sed on each generator as would normally be done for external appliances Control Panel power cables may be fed through either the rear wall or the cable bushings in the bottom of the case Connect the 2...

Page 11: ...ntrol Panels in larger facilities Cable bushings come preattached inside the supply chambers 3x0 25 mm2 or another shielded data cable with at least 3 conductors Data terminal A B and C GND are connec...

Page 12: ...and mark the other ends of the wires within the junction box with their corresponding terminal assignments Rout the other end to a junction box that is situated near or on top to the canopy Control Pa...

Page 13: ...LAN cable straight to the port on the board as seen below LAN cable must be connected to a network switch or to the closest LAN socket Reassemble the housing in reverse order with the smaller LED dis...

Page 14: ...the device has been performed by an authorized partner of ETS NORD AS the equipment is serviced every 12 months after commissioning specified components eg ozone generating equipment have been replace...

Page 15: ...etsnord ee ETS NORD Finland Address Pakkasraitti 4 04360 Tuusula Finland Phone 358 401 842 842 info etsnord fi www etsnord fi ETS NORD Sweden Address J rsj gatan 7 69235 Kumla Sweden Phone 46 70 780...

Reviews: