6
By pressing the "Up" button while in the menu, the
Low Voltage Limit Setting Menu (dG) seen on the
left is accessed. By pressing the "Confirm" button
again, the menu is entered and the low voltage
protection value is set with the "Up / Down"
buttons. The limit value is set at the factory and
changing this value is not recommended.
By pressing the "Up" button while in the menu,
the High Current Limit Setting Menu (YA) seen
on the left is accessed. The menu is entered by
pressing the "Confirm" button and the high current
protection value is set with the "Up / Down"
buttons. High current limit value should be set
according to the power of the electric motor.
By pressing the “Up” button while in the menu, the
Low Current Limit Setting Menu (dA) seen on the
left is accessed. By pressing the "Confirm" button,
the menu is entered and the desired low current
protection value is set with the "Up / Down"
buttons. The low current limit value should be set
according to the power of the electric motor. The
panel has low current automatic reset feature.
When a low current error occurs, the panel makes
automatically resetting the error at increasing
intervals of 2,8,18,32 and 50 minutes. If low current
error occurs again as a result of resetting, the
system is blocked and cannot be operated again.
The "Block (bL)" error must be reset manually by
holding down the Up / Down buttons.
By pressing the "Up" button while in the menu,
the Error Delay Time Setting Menu (GS) seen on
the left is accessed. Error delay time, is the time
until the panel gives a warning after detecting an
error in the system. It is entered into the menu by
pressing the "Confirm" button, and adjusted as
with the "Up / Down" buttons. It is set to 3 seconds
in the factory settings, it is not recommended to
change it except for special applications.
Figure 7. Low Voltage Limit Setting Menu
Figure 9.Low Current Limit Settings Menu
Figure 10. Error Delay Time Setting Menu
Figure 8. High Current Limit Setting Menu
c. Low Voltage Protection Setting Menu
d. High Current Protection Setting Menu
e. Low Current Protection Setting Menu
f. Delay Time Setting Menu