background image

5

www.etna.com.tr

3. Control Board Front Panel

•  General Fault Led: 

This led is ON together with written fault code on 7 segment display 

when low current , high current, low voltage and high voltage protections are active.

•  Up / Down Buttons: 

These buttons enable to surf within menus on 7 segment display and 

they are used to set values of numerical parameters. In addition to this, the fault occured on 

the system can be reset while pressing these buttons together for 5 seconds 

•  Approval Button:

 This button enables to enter submenus and save the parameter already 

set values.

•  Switch Led: 

This led is ON when the pressure swith on the system is active. 

•  ON/OFF Button: 

 This button is used to start-up and switch-off the panel OFF is written on 7 

segment display when the panel is switched-off and there is power supply on the system. 

Voltage value between L1-L2-L3 and neutral is 

displayed in sequence as seen on the left hand side 

when there is no run signal. In case there is run 

signal and system starts operating, pump current is 

displayed.

When the "Confirm" button is pressed in the main 

operation screen, the password menu on the left 

appears. In the password menu, “132” is entered as 

the password with the “Up / Down and Confirm” 

buttons, and the menu is entered by pressing the 

confirm button again. The password is valid for 2 

minutes.

After the password is entered correctly, the High 

Voltage Limit Setting Menu will appear on the 

screen. By pressing the "Confirm" button again, 

it is entered into the menu and the high voltage 

protection value is set with the "Up / Down" 

buttons. The limit value is set at the factory and 

changing this value is not recommended.

4. Menus

a.  Password Menu

b.  High Voltage Protection Setting Menu 

Figure 4. Panel Main Operating Screen

Figure 5. Password Menu

Figure 6. High Voltage Limit Setting Menu

Summary of Contents for Hydropan-Single

Page 1: ...Hydropan Single Operation and Maintenance Manual ...

Page 2: ...re Switch Fault warning leds as well as Up Down buttons used to surf in menus Approval button to confirm parameter changes and ON OFF button System parameters can be set easily by using Up Down Approval buttons located on the front casing Panel On OFF Button Parameter Set Confirmation and Menu Entrance Button No Water Warning Led 7 Segment Display Menu Surf and Parameter Setting Buttons Pressure S...

Page 3: ...3 www etna com tr Connectors Cable Glands Voltage Transformer 7 Segment Display Connection Cable Current Transformers Power Relays Earth Connection Bar Figure 2 Hydropan Single Internal View ...

Page 4: ...etting General Fault No Water and Pressure Switch signal warning leds Pump running currents display on screen during operation Ability to Reset faults Dry running protection with floater Additional dry running protection using minimum current protection algorithm Display all faults on screen Audible fault warning with buzzer Fault history Booster and discharge operating modes Password protection P...

Page 5: ...upply on the system Voltage value between L1 L2 L3 and neutral is displayed in sequence as seen on the left hand side when there is no run signal In case there is run signal and system starts operating pump current is displayed When the Confirm button is pressed in the main operation screen the password menu on the left appears In the password menu 132 is entered as the password with the Up Down a...

Page 6: ... the power of the electric motor The panel has low current automatic reset feature When a low current error occurs the panel makes automatically resetting the error at increasing intervals of 2 8 18 32 and 50 minutes If low current error occurs again as a result of resetting the system is blocked and cannot be operated again The Block bL error must be reset manually by holding down the Up Down but...

Page 7: ...ed when the reservoir is filled with water up to the maximum level is stopped when the water drops to the minimum level and no alarm is given When the water reaches the maximum level again the pump starts automatically and this cycle continues Overflow control can be done with the help of an overflow level switch connected to the SALTER switch terminal In this mode when the SALTER switch input is ...

Page 8: ... the pump operates properly htA dA LOW CURRENT FAULT Before taking the defined measurements make sure that there is no mechanical failure in the pump and that the motor pump group works properly Make sure that the pump suction and discharge valves are not closed Make sure there is water in the reservoir Make sure that there is no air in the system If there is air evacuate the air Check the Low Cur...

Page 9: ...TA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER FLOAT SWITCH U V W L1 L2 L3 BS FAZ NOTR MONOFAZE POMPA İÇİN NOTR FAZ MONOFAZE PANO İÇİN HYDROPAN MONO THREE PHASE FOR SEWAGE AND DRAINAGE PUMPS MOTOR OUTPUT POWER INPUT COM RUN FAULT C TR 30A POWER RELAY 30A POWER RELAY 30A POWER RELAY U V W R S T TRANSFORMER POMPA ENERJİ GİRİSİ POMPA HATA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U V W L1 L2 L3 BS ...

Page 10: ...TA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U N N L1 BS FAZ NOTR MONOFAZE POMPA İÇİN NOTR FAZ MONOFAZE PANO İÇİN HYDROPAN MONO SINGLE PHASE FOR SEWAGE AND DRAINAGE PUMPS FLOAT SWITCH MOTOR OUTPUT POWER INPUT COM RUN FAULT C TR 30A POWER RELAY TRANSFORMER POMPA HATA POMPA DEVREDE ORTAK UF C AF FLATOR C SALTER U N N L1 BS HYDROPAN MONO SINGLE PHASE FOR DEEP WELL PUMPS MOTOR OUTPUT POWER INPUT COM...

Page 11: ...11 www etna com tr NOTES ...

Page 12: ...Dudullu Organize Sanayi Bölgesi 2 Cadde No 14 34775 Ümraniye İstanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr customer service Rev 01 2021 ...