Echo Relay Panel Feedthrough Installation Manual
DMX Control Wiring and Termination
DMX wire preparation will vary with the type of wire and termination kit being utilized. Please
refer to the instructions provided with the DMX termination kit for specifics on the wire
preparation. DMX termination is made to J8 and J9 on the termination board.
After completing the DMX data connections, you must properly terminate the DMX line using
the termination switch (S1) on the relay panel termination board. Data termination eliminates
reflections at the end of the DMX data run.
n/c
n/c
n/c
n/c
n/c
COM
Data + (Red)
Data - (Black)
From DMX
source
If daisy-chaining to
another rack or
DMX device...
The graphic on the left illustrates DMX termination using screw
terminal connectors that are intended for use with Belden 9729
cable (or approved equal).
Screw terminal connectors are supplied in the DMX Preparation
Kit w/ Screw Connector, part number 4100A1012, and shipped
with your Echo Relay Panel.
Be aware that cable other than Belden 9729 may have a different
color code for its wire pairs.
W/BLU
W/GRN
GR
N
BR
N
Data + W/ORG
Data - ORG
Com W/BRN
BLU
The graphic on the right illustrates DMX termination using IDC
connectors that are intended for use with Category 5 solid core
cable (or equivalent cable types). IDC connectors are supplied in
the Cat5 Preparation Kit w/ IDC Connector, part number
4100A1013, and shipped only when ordered separately.
Use a second connector on the DMX Pass-Thru if daisy-chaining to
another panel or DMX device.
Turn on DMX termination
in the last panel/device that
is physically connected in
the DMX chain.
ON OFF RDM
Connect Emergency Contact
The Echo Relay Panel Feedthrough can connect to an external
emergency circuit. Emergency can be triggered by a normally
open or normally closed contact input. In addition, the relay panel
optionally offers a +24Vdc (maximum 25mA) Emergency Out that
provides a feed to a lamp or LED, indicating emergency activity.