System Installation
10
Terminate Wiring
Wire terminations are made to the terminals located on the back side of the fixture.
Step 1:
Locate the provided fixture termination kit.
Step 2:
Connect ground.
a: Locate the pre-stripped black wire with spade terminal.
b: Loosen but do not remove the GND terminal screw on the back of the fixture.
c: Insert the spade terminal under the screw and tighten the screw firmly to secure.
d: Locate a 3 position WAGO inside the termination kit and open all terminal levers.
e: Insert the pre-stripped end of the pigtail into a terminal and close the lever.
f: Strip the ground wire from the power supply to .35-.39” (9-10mm), then insert it
into a terminal and close the lever.
g: If continuing to another fixture in the run, strip the wire .35-.39” (9-10mm) and
insert it into the third terminal and close the lever.
Step 3:
Connect power.
a: Locate the pre-stripped red wire inside of the termination kit.
b: Loosen but do not remove the PWR terminal screw on the back of the fixture.
c: Insert the spade terminal under the screw and tighten the screw firmly to secure.
d: Locate a 5 position WAGO inside the termination kit and open all terminal levers.
e: Insert the pre-stripped end of the pigtail into a terminal and close the lever.
f: Strip the power wire from the power supply .35-.39” (9-10mm), then insert it into
a terminal and close the lever.
g: If continuing to another fixture in the run, strip the wire .35-.39” (9-10mm) and
insert it into the third terminal and close the lever.
Note:
It is acceptable to continue the wiring run for up to 10 fixtures per zone on a power
supply.
Dry Locaons Only
optio
nal C
TRL wi
re
pre-s
tripped
PWR wire
from po
wer suppl
y
to
the next f
ixture