Wiring Diagram
Wiring Diagrams for Emergency Fixtures
Diagram 1 of 2
ELEDR or ELEDRH
Power Load Controller
Power
LED
Clear
Button
Learn
Button
Learn
LED
Load
Red - Load, Switched Hot
Neutral to others
Red - To other loads
Antenna (orange)
Do not cut or cap
Black - Line,
120-277 VAC or 240-347 VAC
@ 50/60 Hz 500 mW max
White - Neutral
Max. Load:
(ELEDR) 20 A @ 120-277 VAC,
Electronic Ballast or LED Driver
(ELEDRH) 20 A @ 240-277 VAC
Electronic Ballast or LED Driver
(ELEDH) 16 A @ 347 VAC,
Electronic Ballast or LED driver
Max. Switching Load
(ELEDR) 20 A @ 120-277 VAC, Electronic Ballast or LED Driver
(ELEDRH) 20 A @ 240-277 VAC, Electronic Ballast or LED Driver
(ELEDRH) 16 A @ 347 VAC, Electronic Ballast or LED Driver
Max. Impulse Voltage: 4000 V
Internal Relay: Type 1.C
Motor load rang: 1.5 HP @ 120 VAC and 3.0 HP @ 277 VAC
Power Load Controller
Power
LED
Clear
Button
Learn
Button
Learn
LED
Load
Normal
Emergency
Load
LED Driver Neutral
Normal Control Sense
Hot
UL924 Emergency
Bypass Relay
(Echoflex Soluons
EREB-AP)
Normal Hot
Normal Neutral
Emergency Hot
Emerency Neutral