Echoflex Installation Guide
Power Load Controller
Power Load Controller
Page 6 of 8
Echoflex
Clear Button
The
[Clear]
button resets the controller either to its pre-commissioned state
or to its factory default state.
To reset to pre-commissioned state:
1. Press the
[Clear]
button until the Power and Learn LEDs start blinking.
2. Release the
[Clear]
button. The Power LED displays a color blink code
to indicate the type and number of devices linked to each channel at
pre-commissioning.
To reset to factory default state:
1. Press and hold the
[Clear]
button until the Power and Learn LEDs start
blinking. Continue to hold for 15 seconds until the LEDs turn solid.
2. Release the
[Clear]
button. The Power LED displays solid red to indicate
factory default state. All links are removed.
Test the Controller
Echoflex provides the controller in either a pre-commissioned state or a
factory default state.
• Pre-commissioned devices are linked, configured, and labelled
according to customer specifications. When powered up, the Power
LED repeats a blink code to indicate the type and number of devices
currently linked to the controller. See
. To test the relay(s), press the
[Learn]
button or use a
linked switch.
• In factory default state, when powered up, the Power LED displays
solid red to indicate the controller has no linked devices. To test the
relay(s), press the
[Learn]
button or link a switch. See relevant switch
documentation.
A maximum of 20 switches or sensors can be linked to one controller.