ArcSystem Installation Manual
Wire and Terminal Specifications
Terminal/Connector
Conduit
Entry
Wire Range/Specifications
Strip
Length
Torque Rating
D1 power input
line/neutral/ground
½ in
conduit
Up to 6 mm
2
(10 AWG) solid or
stranded
7 mm
(1/4 in)
0.8 Nm
(7 in-lb)
D1 HOand D2 power input
line/neutral
½ in
conduit
0.5–10 mm
2
(22–6 AWG)
7 mm
(1/4 in)
0.5 Nm
(4.4 in-lb)
D4 maintained power input
line/neutral
D4 emergency drivers
sense power input
line/neutral/ground
½ in
conduit
0.2–2.5 mm
2
(24–14 AWG)
6.5 mm
(1/4 in)
0.5–0.6 Nm
(4.4–5.3 in-lb)
Power Input
ground
½ in
conduit
2.5–10 mm
2
(6–14 AWG)
10 mm
(3/8 in)
4.0 Nm
(35 in-lb)
DMX In/Thru
RJ45 Connectors
½ in
conduit
Cat5e (or better) minimum 0.2 mm
2
(24 AWG) conductors terminated to
T568B standard
N/A
N/A
Outputs for all D1, D2, and
D4 Series Drivers with Molex
connectors
½ in
conduit
Follow Class 2 wiring methods.
Outputs for D4 drivers with
terminals
½ in
conduit
0.2–2.5 mm
2
(26–14 AWG) using the
provided two-terminal connectors.
Follow Class 1 wiring methods.
6 mm
(1/4 in)
0.4–0.5 Nm
(3.5–4.4 in-lb)
Note:
Maximum supported wire length between One-Cell luminaires and D1 Series
and D2 Series drivers is 15 m (49 ft).
Maximum supported wire length between any load and a D4 Series driver is 10 m
(33 ft).