Rectifying problems
77
6
Rectifying problems
Ash screw jammed
If the ash screw is stuck, a corresponding warning will
be displayed on the screen.
The most common cause of a blockage is a full
ash bin. So first check to see how full the ash bins
are and empty them. If the ash bin is not full, then it can
be assumed that a foreign object is blocking the ash
screw.
1. End the boiler's heating mode with the On/Off
switch
in the boiler overview window. As
soon as the [Switched off] operating condition is
displayed, switch off the boiler with the mains
switch.
2. Detach the ash bins from the boiler and check the
visible part of the ash screw. The foreign body may
already be found at the end of the ash screw,
where it can be removed.
Fig. 6-1: Tilting grate ash screw
3. If no foreign body is visible, it is probably in the
combustion chamber under the tilting grate.
Remove both combustion chamber covers from
the combustion chamber.
4. The grate cannot be tilted by hand. Tipping is done
by starting de-ashing with the [De-ash]
button.
The grate tilts and remains in this position for ap-
proximately 15 seconds.
WARNING!
Danger of crushing due to tilting grate
When the grate is tilted, switch off the boiler with
the mains switch. This causes the grate to remain
in this position so injuries are prevented.
Now the ash screw under the tilting grate is
accessible and the foreign body can be removed.
5. After removing the foreign object, replace the
combustion chamber covers and reattach the ash
bins to the boiler.
6. Switch on the boiler with the mains switch. To
check, start de-ashing by pressing [De-ash]
.
If no error message appears, switch the boiler back on
with the On/Off
switch. If there is still a
blockage, the ash screw must be removed.
Removing the ash screw
If the ash screw is jammed or the foreign body
cannot be removed, the ash screw must be
removed.
Summary of Contents for 13180LP-T
Page 1: ...2018 05 24 EN 0000000313 V 005 3 43 0 3308 93222 001 Pellet boiler 180 220 kW Operation ...
Page 29: ...ETAtouch controller Getting to know the control system 29 ...
Page 39: ...ETAtouch controller BufferFlex function block 39 ...
Page 47: ...ETAtouch controller Buffer function block 47 ...
Page 51: ...ETAtouch controller Hot water tank function block 51 ...
Page 55: ...ETAtouch controller Fresh water module function block 55 ...
Page 69: ...ETAtouch controller Solar function block 69 ...
Page 87: ......
Page 88: ...www eta co at www eta co at downloads DOWNLOAD ...