5.3
Hardware Limits
To operate safety, please set the relevant protection parameters before the formal test.
Operation steps:
Click "Hardware Limits" to enter the panel (Figure 5-7). After setting the parameters, click
"Apply".
Figure 5-7 Hardware limits panel
Table 5-4
Number Name
Note
①
Three-phase Parallel
(Phase A)
Three-phase parallel output (-1P option), the
three-phase parallel output is valid after checking
②
OCP (Max~120%)
Overcurrent protection value, when the output current
exceeds the value, the power output will be off.
③
OVP (Max~110%)
Overvoltage protection value, when the output current
exceeds this value, the power output will be off.
④
OPP [kW]
Overpower protection value, when the output power
exceeds this value, the power output will be off.
⑤
Output Peak Current
Limit
Maximum current limit value, when the output current
exceeds this value, it will be limited below the current