GB
17
• EPL-Transceiver/TLA
- There may only be one EPL-Transceiver/TLA per group.
- The sub-group “
e
” is preset to 15 (fixed).
- The time setting is set via the right rotary knob “
e
”
(fig. 1)
:
Position “e”
Time setting in minutes
0
ON/OFF function as for EPL-Receiver/10A
1
1
2
2
3
3
4
5
5
8
6
10
7
12
8
15
9
20
10
25
11
30
12
45
13
60
14
90
15
120
• EPL-Transmitter/RC
From
Version B
onwards (see type plate), the light control can be disabled for
12 hours using a 2-way button on the RCi motion detector. To do this, program an
EPL-Transmitter/3 in the same main group “
g
” and the same sub-group “
e
” as the
EPL-Transmitter/RC and simply connect a 2-way button
(see page 113)
.
Press and hold (> 3 seconds) to switch the light ON for 12 hours, press and hold
(> 3 seconds) to switch the light OFF for 12 hours. A short key press (< 3 seconds) will
switch the light ON or OFF and disable the continuous function.
The light will then be controlled by the RCi motion detector again.