Page 4 of 4
D A T A S H E E T
ESL85001-0632
Not to be used for installation purposes.
Issue 1
10-06-16
North America
T 885-286-8889
Asia
T 852-2907-8108
F 852-2142-5063
Australia
T 61-3-9239-1200
F 61-3-9239-1299
Europe
T 32-2-725-11-20
F 32-2-721-40-47
Latin America
T 561-998-6114
F 561-994-6572
Specifications subject to change without notice.
© 2012 Interlogix.
Interlogix is part of UTC Climate Controls & Security,
a unit of United Technologies Corporation.
All rights reserved
interlogix.com
Specifications
Input voltage
12 or 24 VDC supplied by UL 985 or UL 864 listed control panel
or resettable auxiliary power supply
Current consumption
Normal
Alarm
20 mA
40 mA (75 mA in test)
Alarm relay
Type
UL rating
150 mA at 33 VDC
Form C
Zone
Common trouble relay
Type
UL rating
150 mA at 33 VDC
Normally opened held closed with power applied
Common
Sensor life
10 years from date of manufacture
Sounder
85 dB
Compatible control panel
Listed to UL 985 or 864 standards
Compatible electrical box
2-1/2 in. (64 mm) single-gang
Wire size
14 to 22 AWG (0.25 to 2.0 mm²)
Dimensions (W × L × D)
Detector
Adapter plate
3.1 × 4.6 × 1.4 in. (7.8 × 11.7 × 3.6 cm)
4.5 × 6.5 × 0.2 in. (11.4 × 16.5 × 0.5 cm)
Color
White
Operating environment
Temperature
Relative humidity
40 to 100 °F (4.4 to 37.8 °C)
10 to 90% noncondensing
CO sensitivity
70 ppm, 60 to 240 minutes
150 ppm, 10 to 50 minutes
400 ppm, 4 to 15 minutes
Ordering Information
Model
Description
260-CO
SafeAir Carbon monoxide detector, alarm & trouble relays,
sounder, end-of life signal, 12/24VDC
250-COPLT-5PKG
Adaptor plate for use when replacing the 240-COe CO detector
with a 260-CO
ESL 405-01
Polarity Reversal Module, 24 VDC
ESL 405-03
Polarity Reversal Module, 12 VDC
ESL 405-05
Polarity Reversal Module, 12/24VDC
CO Gas Test Spray
Functional CO gas test spray Solo C-6 from SDI
(www.sdifire.com) available through security distribution.