Page 3 of 4
D A T A S H E E T
ESL85001-0632
Not to be used for installation purposes.
Issue 1
Wiring
Alarm
IDC
EOL device
Single device,
single zone
Power
Multiple devices,
single zone
C
NC
NC
NO
C
C
NC
NC
NO
C
C
NC
NC
NO
C
EOL device
EOL device
ESL 405
Polarity Reversal
Module
Alarm
IDC
Control Panel
Power NAC
Multiple devices,
separate alarm, trouble zone
C
NC
NC
NO
C
C
NC
NC
NO
C
C
NC
NC
NO
C
EOL device
EOL device
ESL 405
Polarity Reversal
Module
Alarm
IDC
Control Panel
Power NAC
SUPV
IDC
Tandem Interconnect:
Use a Single Circuit Reversal
Module when wiring multiple
260-CO detectors for tandem
interconnect. On alarm, the
module disconnects the detec-
tor from its normal power supply
and applies reverse polarity from
the notification appliance circuit.
This causes the sounders to
activate on other 260-CO detec-
tors that are on the same loop.
Only the initiating detector will
sound
and
blink red. All others
in tandem mode will sound but
not blink red.
Installation
The 260-CO Carbon Monoxide Detector is a four-wire device
designed to use a Class 2 output from a control panel or auxiliary
power supply Listed to UL 985 or 864 standards.
All wiring must conform to the NFPA 70 National Electric Code, UL
2075, NFPA 720, and applicable codes. Use 14 to 22 AWG wire.
The 260-CO/240-COe
adapter plate
Use a 250-COPLT adaptor
plate when replacing a 240-
COe with a 260-CO to cover
any paint discoloration left
behind.