EsiWelma Srl 

URD20SL_en.doc - rev. 0 

CO

2

 gas detectors – URD20SL 

24/09/2010 

Gas detection systems for industrial environments 

4/8

 

Electrical Installation 

 
 

 
 
 
 
 
 

Terminal board and 
electrical connections 
 
 
 
 
 
 
 
 
 

 
 

Cabling:

 

 
 
 

 

Configuration: 

 
 
 
4…20mA Output 
reference selection: 
 
 
 
 
 
 
4...20mA signal 
operating mode 
configuration: 
 
 

 

Setting threshold limit 
values: 
 
 

CAUTION:  

 Make the area safe and make sure that the device power supply is 

off before cabling and configuration operations.

 

Install the sensor in compliance with laws in force. 
The cable gland provided on the housing is used for cable entry. 
Ground the sensor using the internal grounding system. 
 

Ground connection 
 
 
Terminal Board TB1 

+

12…24Vdc

 


4…20mA

 

+

 
JP2 jumper circuit 

 

S1 DIP switch 

 

 

 

 
 

 
 

Depending on the connecting distance, use at least 3-core cable, min diameter 
0.75mm

2

 up to 100mm

2

, 1mm

2

 up to 200mm

2

 , 1.5mm

2

 up to 500mm

2

 . 

Use shielded cable where there is a risk of electromagnetic interference.  
If a relay card is used, use multi-core cable suitable for the number of connections. 

 

Default settings of the sensor are shown in the “Technical Specifications” chapter. 
In order to change the default settings, switch off the power supply, input the new 
settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram, 
then power-up again; in particular: 

 

The default setting for the 4-20mA signal is the negative power signal. Output 
reference selection should be made by JP2 triple of jumpers; to change this setting, 
operator has to move 

JP2

 jumpers as shown in the figure: 

Caution:

 if the default settings are changed, 

the connections on the 

TB1

 terminal board 

will be inverted.

 

     

     Ref. at  -  (default)            Ref. at    

 

 

To set the operating mode of the 4...20mA signal, it is necessary to use the 5th 
selector of the DIP switch at 

S1

; in particular: 

 
 

 

                                            Proportional                        Threshold mode 

 

To set the threshold limit values of the optional relay card, or of the threshold operating 
mode of the 4...20mA signal, it is necessary to use the first four selectors of the DIP 
switch at 

S1

; in particular, the thresholds, given in full scale percentage, will be: 

 
 
 
 
 
 
 
 
 
 
 

 

Sensor 
card 

Relay card 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

CN4 connection for handheld 
terminal 

Connection slot 
for relay card 

CUSTOM (*)              3, 5, 10%               5, 10, 15%             5, 10, 20%             10, 15, 25%           10, 15, 30% 

10, 20, 40%             10, 25, 35%            15, 25, 40%            15, 30, 45%            25, 35, 50%           20, 40, 60% 

(DEFAULT) 

20, 40, 80%            -----------------Future implementations------------------ 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

CU

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

(*) When the first four selectors
of the DIP switch are in OFF
position, the threshold limit
values can only be set by the

TUS40

 handheld terminal. 

If this is selected without using
the handheld terminal, the
detector will automatically set
the default threshold limit
values.    To set the detector
with the handheld terminal, see
the dedicated instruction
manual. 

Summary of Contents for Sensigas URD20SL

Page 1: ...n dioxide leaks or emissions in industrial environments hospitals fermentation plants greenhouses stables and more in general where carbon dioxide is stored generated or produced URD20SL sensors can b...

Page 2: ...d resistor up to 200 at 12Vdc power supply 200 700 at 24Vdc power supply Operating Temperature Storage Temperature 20 50 C 20 70 C Relative Humidity without condensing Operation Storage 15 90 RH 45 75...

Page 3: ...that of air so it tends to collect at floor level in closed unventilated environments Therefore the sensor must be installed about 30 cm above the floor level Take into consideration the following sp...

Page 4: ...be made by JP2 triple of jumpers to change this setting operator has to move JP2 jumpers as shown in the figure Caution if the default settings are changed the connections on the TB1 terminal board wi...

Page 5: ...ns below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connectio...

Page 6: ...cal installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The...

Page 7: ...o the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 gas calibration kit and the TUS40 handheld terminal which must be connec...

Page 8: ...or industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Re...