EsiWelma Srl 

URD20SL_en.doc - rev. 0 

CO

2

 gas detectors – URD20SL 

24/09/2010 

Gas detection systems for industrial environments 

1/8

 

 

 

 

 

 

Gas detectors 
Carbon dioxide  (CO

2

IP55 protection rating 

 

URD20SL 

 

 

 

 

 

 

 

 

 

 

 

 

11…28Vdc power supply. 

Nondispersive infrared (NDIR) sensor designed for the detection of carbon dioxide 
(CO

2

). 

Up to three alarm thresholds plus sensing element fail. 

LED on sensing element body to indicate operating status. 

Automatic countdown of sensor life.

 

Use 

The URD20SL detectors are used to detect the presence of carbon dioxide (CO

2

), in 

non-classified areas. 

It detects carbon dioxide leaks or emissions in industrial environments, hospitals, 
fermentation plants, greenhouses, stables and, more in general, where carbon dioxide 
is stored, generated or produced. 

URD20SL sensors can be used in stand-alone mode with 4…20mA output or with an 
optional voltage-free contact relay card having the following four digital outputs: 

Pre-alarm, 1

st

 alarm threshold, 2

nd

 alarm threshold, sensor fail. 

Operation 

If there is a gas leakage, the detector compares the measured concentration value 
with the threshold limit setpoints and energises the associated relays. Information on 
the measured concentration value is always at the 4…20mA output. 

Ordering 

To order, simply state the part number: 

URD20SL

For special versions, on request, please contact Customer Service. 

 

Summary of Contents for Sensigas URD20SL

Page 1: ...n dioxide leaks or emissions in industrial environments hospitals fermentation plants greenhouses stables and more in general where carbon dioxide is stored generated or produced URD20SL sensors can b...

Page 2: ...d resistor up to 200 at 12Vdc power supply 200 700 at 24Vdc power supply Operating Temperature Storage Temperature 20 50 C 20 70 C Relative Humidity without condensing Operation Storage 15 90 RH 45 75...

Page 3: ...that of air so it tends to collect at floor level in closed unventilated environments Therefore the sensor must be installed about 30 cm above the floor level Take into consideration the following sp...

Page 4: ...be made by JP2 triple of jumpers to change this setting operator has to move JP2 jumpers as shown in the figure Caution if the default settings are changed the connections on the TB1 terminal board wi...

Page 5: ...ns below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connectio...

Page 6: ...cal installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The...

Page 7: ...o the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 gas calibration kit and the TUS40 handheld terminal which must be connec...

Page 8: ...or industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Re...