background image

EsiWelma s.r.l.

    

rev. 02 of 01-09-10 / pg. 4 

___________________________________________________________________________________________ 

Power supply (see available models) 

230Vac 

±

 10% or 12Vac/dc 

±

 10% or 12…24Vac/dc 

Frequency 

50/60Hz 

Consumption 

2 VA 

Command outputs 

SPDT relay - capacity of the contact 250Vac 5(3)A 

1

st

 and 2

nd

 alarm threshold 

100 and 300ppm

(1)

 of Carbon Monoxide 

Threshold limit value 

Between 12m and 12s at 100ppm and 300ppm, respectively 

Operational lifetime of a detector 

5 years from installation 

Max detectable area  

approx. 40 m

2

  

Visual warnings 

Green LED (power is on) 

Yellow LED (warm-up / sensor fail) 

Red LED (gas alarm) 

Audible alarms: 

Piezoelectric buzzer 85dB at 1m 

Protection Rating 

IP42 when correctly installed 

Product conformity standard 

     EMC Electromagnetic Compatibility 

           Low voltage (LVD) 

UNI CEI 70032 

EMC 2004/108/EC – EN50270

 

LV 2006/95/EC – EN60669-1 

Operational room temperature 

-10...+40 °C  (storage  –20…...+70 °C) 

Ambient humidity allowed: 

30... 90% RH (storage 0...+95% RH) (non condensing) 

Dimensions 

For installation in 503 type recessed mounting box 

• 

142 x 100 x 72mm with ESN.KW wall-mounting adapter 

• 

142 x 120 x 100mm with ESN.KT/KC table-top adapter 

Enclosure 

ABS/PC UL94-V0 flame retardant 

(1) 

ppm =

 

parts per million of concentration of gas in the air. 

___________________________________________________________________________________________ 

Wiring diagrams: 

Example a): - Command of a solenoid valve (Normally Open); in this mode, when the alarm threshold is ex-

ceeded the solenoid valve will close and therefore the gas supply will be cut-off. 

Example  b):  -  Command  of  a  solenoid  valve  (Normally  Closed)  and  of  visual  and  audible  alarms;  in  this 

mode, the solenoid valve will close and therefore the gas supply will be cut-off: when the alarm 

threshold  is  exceeded,  if  there  is  a  power  failure  and  if  the  actual  solenoid  valve  is  discon-

nected. 

 

___________________________________________________________________________________________ 

To be filled in by Installer

 

Installer's stamp

 

Installation site 

………………………………………………………………. 

Product order number 

………………………………………………………………. 

Part number  

………………………………………………………………. 

Installation date 

………………………………………………………………. 

 

___________________________________________________________________________________________ 

Technical 
specifications

 

Connection 
diagrams

 

Installation 
data

 

230Vac  or  12Vac/dc  or  12…24Vac/dc

 

4

 

5

 

a) 

ESN.I.O..

 

2

 

 1 

NA 

230Vac  or  12Vac/dc  or  12…24Vac/dc

 

4

 

5

 

b) 

ESN.I.O..

 

2

 

 1 

NC 