EsiWelma s.r.l.

    

rev. 02 of 01-09-10 / pg. 1 

 

 

E218.302

 

 

Carbon Monoxide detectors 

for homes, recreational vehicles and similar sites 

 
Conformity standard UNI CEI 70032 

ESN.I.O..

 

 

 

 

 

 

 

___________________________________________________________________________________________ 

Electronic carbon monoxide detectors with time-varying alarm threshold and two calibration points for 
homes, recreational vehicles and similar sites. 
230Vac, 12Vac/dc or 12…24Vac/dc power supply, depending on the model. 
Relay command output with double insulation voltage free contact, so suitable for any kind of solenoid 
valve or other command and alarm device. 
Possibility of parallel connection of more than one detector, also for monitoring different gases. 

___________________________________________________________________________________________ 

Use

 

The  ESN.I.O..  detectors  can  be  used  to  provide  a  visual/audible  alarm  and  to  control  other 
alarm  transmitters  or  actuating  devices,  in  the  presence  of  carbon  monoxide  concentrations 
that pose a hazard to humans from gas poisoning.

 

___________________________________________________________________________________________ 

Operation

 

The  detector  will  enter  a  warm-up  phase  after  power-up;  this  will  take  about  60"  and  during 
this  time  the  detector  is  inoperative.      At  the  end  of  the  warm-up  phase,  the  detector  enters 
normal operation mode, and will continue in this state until it detects gas.

 

Gas detection 

The  monitoring  algorithm  used  for  gas  detection  is  “time-varying  alarm  threshold”  that 
considers both the concentration of the gas and the time it is detected. A threshold level one, 
set  at  100ppm

(1)

  sets  off  the  time  meter;  if  the  concentration  remains  at this value the alarm 

will  activate  after  12  minutes;  at  300  ppm,  the  detector  will  enter  alarm  condition  after  the 
concentration  remains  at  this  level  (or  at  a  higher  level)  for  only  12  seconds.  Concentration 
values of between 100 and 300ppm require proportionately intermediate times of between 12 
seconds and 12 minutes. 
Once the alarm condition ceases to exist, or the level descends to below 11ppm, for a given 
time that depends on how quickly the concentration descends, the detector will be restored to 
normal operation. 

(1) 

ppm =

 

parts per million of concentration of gas in the air.

 

___________________________________________________________________________________________ 

Power supply 

Detector 

230Vac 

12Vac/dc 

12…24Vac/dc 

Recessed 

ESN.I.O.x 

ESN.I.O.x.D 

ESN.I.O.x.E 

Wall-mounted 

ESN.I.O.x + ESN.KW 

ESN.I.O.x.D + ESN.KW 

ESN.I.O.x.E + ESN.KW 

Table-top 

ESN.I.O.x + ESN.KT 

ESN.I.O.x.D + ESN.KT 

ESN.I.O.x.E + ESN.KT 

Table-top (precabled) 

ESN.I.O.x + ESN.KC 

ESN.I.O.x.D + ESN.KC 

ESN.I.O.x.E + ESN.KC 

The letter A or B inserted in field x of the product order number indicates the type of detector, i.e.: 
A = with relay command output   

B = without relay command output (visual/audible alarm) 

___________________________________________________________________________________________ 

Available 
models  
and ordering 
information

 