background image

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11340 V2.0 R1.0  Manual 

Page 2 of 9 

 
 
 

1-Wire Controller 2 configuration

 

For the configuration of the 1-Wire Controller 2, we provide a very powerful and user-friendly software 
(Config Tool 3) free of charge. Within the software you have the complete documentation at hand at any time 
and up-to-date, as it is automatically updated via the Internet. We provide the software via the article 
download area of our website and via the configuration software ESERA Config Tool 3. 
 

System time / real time clock 

No real time clock with battery buffering available in your system? No problem at all. Our 1-Wire Controller 2 
is providing time and date as real time clock including an integrated backup battery. Data plausibility check is 
possible at any time. 
 

Power supply 

For power supply, the 1-Wire Controller 2 has a power supply input of  
9 - 30 VDC and is therefore equally suitable for 12 V and industrial 24 VDC supplies.  
You can find suitable DIN rail or plug power supplies in our webshop.  
 

Auto-E-Connect® Support 

The ESERA 

Auto-E-Connect®

 1-Wire Plug and Play system will be used for the  

1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors 
and actuators on the 1-Wire bus. It is optimized for industrial applications and 
enables significant added value beyond the sensor and chip data. 
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable 
libraries and outputs fully formatted data. 
The Auto-E-Connect functionality will be available from mid-2020 via 1-Wire Controllers, 1-Wire Gateways and  
1-Wire ECO from ESERA available. 
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in 
the download area for this article in the ESERA Webshop. 
 

Technical data 

Data Interface: 

ESERA ASCII text protocol 

Ethernet Interface:  

TCP/IP or UDP     

  

 

- 10/100 MBit Ethernet Interface (RJ45)  

 

- Auto Negotiation (Full-duplex and Half-duplex)  

 

- Auto MDI/MDIX     

 

- Support for DHCP and fix IP-address  

 

- DNS support 

 - Support user password for security 

 

- DYN-DNS server support 

Firmware Update:  

via ESERA Config-Tool 3  

Power supply:   

15 

– 30 VDC  

Power consumption:  

maximum 1 A   

1-Wire interface:  

1-Wire Bus (12 V maximum 250 mA, 5 V maximum 200 mA, GND und data)  

Protective circuits:  

ESD protection and reverse polarity protection   

Connection:   

Screw terminals (up to 2,5 qmm wire cross section)  

Output voltage:  

12 V maximum 250 mA (+/- 10 %), 5 V maximum 200 mA (+/- 10 %) 

 

overload-proof and short-circuit-proof 

 

Isolation:   

Galvanic separation among data and 1-Wire interface  

 

Ambient conditions 

Temperature, operation   -10 °C up to +55 °C (extended temperature range available upon request)

 

Air humidity:   

10 

– 92 % (non-condensing)  

Protection system:  

IP20  

Protection class:  

III  

Dimensions:   

35 x 90 x 70mm (WxHxD)  

 
 
 
 
 
 

Summary of Contents for Auto-E-Connect 11340

Page 1: ...ing to the safety notes 2 Product description You can communicate with your smart home or industrial controller e g ESERA Station IP Symcon Loxone or FHEM via TCP or UDP protocol with the 1 Wire Controller 2 Autonomous management The 1 Wire Controller 2 is designed for the autonomous management of a 1 Wire Network You no longer need to worry about 1 Wire commands or formulas for evaluating sensor ...

Page 2: ... of 1 Wire sensors and actuators on the 1 Wire bus It is optimized for industrial applications and enables significant added value beyond the sensor and chip data The Auto E Connect function automatically recognizes ESERA chips sensors and actuators starts suitable libraries and outputs fully formatted data The Auto E Connect functionality will be available from mid 2020 via 1 Wire Controllers 1 W...

Page 3: ... 3 Interference radiation RoHS 7 Display LED The module has various display LEDs In the following the function of the displays Display Description Function LED Green PWR Display for supply voltage LED Green DATA LED flashes 3 times after power on Flashes at 1 Wire activity Flashes while transferring data by the data interface Flashes very quickly if KAL Receive has been activated and the KAL messa...

Page 4: ...c duplication of this user guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11340 V2 0 R1 0 Manual Page 4 of 9 8 Connection www esera de ...

Page 5: ...for digital output 5 26 Digital output 5 normally open contact max 5A 30 Reset Button inside 32 GND negative 1 Wire Bus 33 1 Wire Data 34 5 V voltage supply for 1 Wire Bus max 200 mA 35 12 V voltage supply for 1 Wire Bus max 250 mA Module bottom side supply voltage digital input and analog output 1 GND negative digital input isolated to negative supply 2 digital input 1 10 30 VDC 3 digital input 2...

Page 6: ... complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11340 V2 0 R1 0 Manual Page 6 of 9 9 Connection example 1 Wire Controller sensors and actuators and termination www esera de ...

Page 7: ...gration in FHEM For the integration into the open source automation software FHEM we provide a software module for easy integration of the 4 fold analog input into FHEM via 1 Wire Controller 1 Wire Gateway Thus evaluation scripts are no longer necessary Details can be found on the ESERA website under Compatible controllers Central FHEM integration Further details can be found on our webpage https ...

Page 8: ...where flammable gases vapours or dust are present or could be present 18 Assembly The installation site must be protected against moisture The device may only be used in dry indoor rooms The device is intended for mounting inside a control cabinet as a stationary device 19 Disposal note Do not dispose of the device within the household waste According to the directive concerning old electrical and...

Page 9: ...r damages for example for non performance fault in contracting breach of secondary contractual obligations consequential damages damages resulting from unauthorized usage and other legal grounds are excluded Excepting to this ESERA GmbH accepts liability for the absence of a guaranteed quality resulting from intent or gross negligence Claims made under the Product Liability Act are not affected If...

Reviews: