10
Isotherm
3.3.1 Alarm Setting
The high point temperature alarm setting can be adjusted. Please note the alarm value is a relative setting.
Range for alarm setting: 2°C~10°C (If the refrigeration system is active, use 2
o
C). In case, actual temperature in
equipment is equal or higher than temperature set point + alarm value, buzzer will sound and red light of
"Alarm" indicator will flash.
Step
Description
Button
Display
1
Press MENU button until the display shows Setting. Press SET TEMP to
enter the menu.
MENU –
SET TEMP
2
Press MENU button until the display shows Alarm.
MENU
3
Press UP/DOWN button to choose the alarm value. Press SET TEMP to
save setting.
UP/DOWN –
SET TEMP
3.3.2 Timer Setting
3.3.2.1 Turning the timer ON and OFF
Step
Description
Button
Display
1
Press MENU button until the display shows Setting. Press SET TEMP to
enter the menu.
MENU –
SET TEMP
2
Press MENU button until the display shows Timer.
MENU
3
Press UP/DOWN button to set the timer ON/OFF. Press SET TEMP to save
setting.
UP/DOWN –
SET TEMP
3.3.2.2 Set timer (0000 – 9999 seconds)
Time is set in normal operation, not in main menu. So exit the menu to set timer.
Step
Description
Button
Display
1
Press SET TEMP button to start the setting.
SET TEMP
2
Press MENU button until the display shows Timer.
MENU
3
Press UP/DOWN button to set required time. Press SET TEMP to save
setting.
UP/DOWN –
SET TEMP
NOTE:
The timer starts when the actual temperature is equal/larger than the set point temperature. Do not turn off the
timer, once it starts.
The remaining time can be checked using DOWN button during normal operation.
is shown on “Actual” display and buzzer sounds 4 times as counting ends. All buttons are locked. Re-start the
device to reactivate the buttons.
Timer will not be saved and assumed to be
as equipment is re-started.
3.3.3 Password (PIN) Setting
The PIN consists of 4 alphanumeric digits. When set to 0000, the PIN is disabled; otherwise the MENU and SET
TEMP buttons functions require PIN.
3.3.3.1 Set PIN (0000 – 9999; 0000 – pin disabled)
Step
Description
Button
Display
1
Press MENU button until the display shows Setting. Press SET TEMP to
enter the menu.
MENU –
SET TEMP
2
Press MENU button until the display shows PIN.
MENU
3
Press UP/DOWN button to set the PIN’s digit. Press SET TEMP to confirm
the number and move to the next digit.
UP/DOWN –
SET TEMP
4
Repeat step 3 until the fourth digit. Once the fourth digit is chosen,
pressing SET TEMP button will save the PIN.