- ENGLISH -

THW01B0001EV 027284 150716

9

-  By modifying the relay operating logic, the setpoint values 

will be automatically taken back to the default values for the 

mode set.

-  The programmable thermo-hygrostat leaves the factory set in 

the dehumidifying mode.

The procedure below must be followed to modify the operating logic:

1.

 Select parameter ‘ 

dE-H

 ’ and press ‘ 

OK

 ’; the display will show the 

actual adjustment mode and the ‘ 

P

 

‘ icon will flash.

2.

 Press the ‘   ’ and ‘   ’ keys to select the desired adjustment 

mode; every modification is memorised automatically.

 ‘ 

dEUM

 ‘:  Dehumidification

 ‘ 

HUMI

 ‘:  Humidification

3.

 To go back to the list of user parameters, press ‘ 

OK

 ’.

4.

 To exit user parameters setting and restore normal operation, press 

‘   ‘ or do not press any key for 10 seconds.

During  normal  operation,  dehumidification  or  humidification  mode 

activation is indicated by the ‘   ‘ icon on.

C-dP

’ DEW POINT MANAGEMENT

Using this parameter it is possible to enable/configure the Dew Point 

control in order to prevent the formation of surface condensate.
Proceed as follows to set this parameter:

1.

 Select parameter ‘ 

C-dP

 ’ and press ‘ 

OK

 ’; the display will show the 

actual setting and the ‘ 

P

 

‘ icon will flash.

2.

 Press the ‘   ’ and ‘   ’ keys to select the desired adjustment 

mode; 

every modification is memorised automatically.

  The adjustment modes are the same:

OFF

:  Dew point control disabled.

d-EF

:  Dew point control with remote probe on underfloor plants.

d-EC

: Dew point control with remote probe on metal ceiling.

d-FP

: Dew point control enabled on foxed points; adjustment can take 

place on internal sensor or remote sensor (to set in the ‘ 

rEG

 ’ 

parameter).

 

For every adjustment mode, which activates dew point management, 

it is possible to modify the factory setting by proceeding as follows:

3.

 On selection of the adjustment mode suitable for the plant to be 

managed, press ‘ 

OK

 ’.

4.

 Press the ‘   ‘ and ‘   ‘ keys to modify the value; every 

modification is memorised automatically.

 

If the ‘ 

d-FP

 ’ parameter is selected, by pressing ‘ 

OK

 ‘, sit 

is possible to use the ‘   ‘ and ‘   ‘ keys to modify the two 

thresholds in order to prevent the temperature reaching the dew 

point:

 

TF1

:  second lower threshold of the dew point (expressed in °C).

 TF2

:  first lower threshold of the dew point (expressed in °C).

  To modify the value of the two thresholds, select 

TF1

 or 

TF2

 and 

press ‘ 

OK

 ’ and then use the ‘   ‘ and ‘   ‘ keys to modify the 

value; every modification is memorised automatically.

Adjustment

mode

Any

sub-parameters

Range of 

adjustment 

OFF

-

-

d-EF

SMF

1.0°C .. 10.0°C

d-EC

SMC

1.0°C .. 10.0°C

d-FP

TF1

5.0°C .. 24.8°C

(Limit TF1=TF2-0.2°C)

TF2

5.2°C .. 25.0°C

5.

 To go back to the list of user parameters, press ‘ 

OK

 ’ and then the 

‘   ‘ key.

6.

 To exit user parameters setting and restore normal operation, press 

‘   ‘ or do not press any key for 10 seconds.

WARNING

When the regulation modes ‘d-EF’, ‘d-EC’ o ‘d-FP‘ are shown, the 

calculated dew-point (dP) value will be alternately shown.

Dew point control limitations

-  When the dew point control is active in modes ‘

d-EF

‘ or ‘

d-EC

‘, 

the parameter ‘

rEG

‘ (room temperature regulation sensor) will be 

automatically set to the internal sensor. The dew point temperature 

will be calculated according to the temperature measured by the 

internal sensor, meanwhile the ceiling or floor temperatures will be 

calculated based on the remote sensor.

- When the dew point regulation is active in mode ‘

d-FP

‘ the 

regulation sensor will be the internal one, meanwhile the external 

sensor will only be used for the measured temperature.

- The dew-point temperature will always be calculated according 

to the temperature measured by the internal sensor. Once the 

parameter ‘

rEG

‘ is reached, the label ‘

indP

‘ will be shown on the 

display, together with the ‘

SET%RH

‘ icon flashing. If the regulation 

sensor has to be modified, the settings for the dew-point control 

must first be modified.

-  The dew-point regulation is active only when the regulator is set on 

cooling and dehumidification.Otherwise the access to parameter ‘

C-dP

‘ 

will not be allowed and the label ‘

nOdP

‘ will be shown instead.

-  The dew-point measurement is taken on a regular basis, according 

to the value set in the parameter ‘

cndP

‘, from 3 minutes up to a 

maximum of 27 minutes.

-  When the dew-point regulation is activated either when restarting 

from the states OFF, housekeeping or vacations, or when 

parameters ‘

d-EF

‘, ‘

d-EC

‘ or ‘

d-FP

‘ have been changed; in this case 

the regulator will restart for 1 minute with all relays in NC position, 

in order to avoid sudden activations. After this phase the normal 

regulation will be activated.

For further details regarding the parameters involved in the control of 

the dew point, see the following paragraphs.

d-EF

’  Dew  point  control  with  external  probe  on  underfloor 

plants.

When the dew point regulation is active with the ‘C-dP’ parameter 

set on ‘

d-EF

’, the regulator will control both systems attached for the 

cooling and de-humidification according to the comparison between 

the dew-point temperature and the temperature measured by the 

external sensor, thus applying the settings of the regulation ‘

d-EF

’ 

regulation.
The following graphics describe the dew point control mode.

HYdP

hysteresis

PRIORITY ON 

THERMOSTAT

PRIORITY ON 

DEHUMIDIFIER

PRIORITY ON

dp

cooler

dehumidifier

TE+SMF

TE+SMF+ HYdP

0

°C

HYdP

hysteresis

PRIORITY ON

dp

dp

Where:

dP

:  dew point (see table 1).

TE

:  External temperature measured

SMF

:  dew point increase set in the sub-parameter ‘ 

d-EF

 ‘.

HYdP

: dew point hysteresis equal to 0.5°C (cannot be modified).

d-EC

’  Dew point control with external probe on metal ceiling.

When the dew point regulation is active with the ‘

C-dP

’ parameter 

set on ‘

d-EC

’, the regulator will control both systems attached for the 

cooling and de-humidification according to the comparison between 

the dew-point temperature and the temperature measured by the 

external sensor, thus applying the settings of the regulation ‘

d-EC

’ 

regulation.

The following graphics describe the dew point control mode.

HYdP

hysteresis

PRIORITY ON 

THERMOSTAT

PRIORITY ON 

DEHUMIDIFIER

PRIORITY ON

dp

cooler

dehumidifier

TE+SMC

TE+SMC+ HYdP

0

°C

HYdP

hysteresis

PRIORITY ON

dp

dp

Dove:

dP

:  dew point (see table 1).

TE

:  External temperature measured

SMC

:  incremento del punto di rugiada impostato nel sottoparametro 

‘ 

d-EC

 ‘.

HYdP

: dew point hysteresis equal to 0.5°C (cannot be modified).

d-FP

’  dew point control on fixed points

If the dew point control function, ‘ 

C-dP

 ’, is activated on ‘ 

d-FP

 

’,  the programmable thermo-hygrostat controls the cooling and 

dehumidification  devices  on  the  basis  of  the  comparison  of  the 

temperature value of the dew point calculated and the temperature 

values relative to the dew points set in the sub-parameters ‘ 

TF1 

’ 

and ‘ 

TF2

 ’.

The following graphics describe the dew point control mode.

HYdP

hysteresis

OFF

PRIORITY ON 

THERMOSTAT

cooler

dehumidifier

TF1

0

°C

HYdP

hysteresis

PRIORITY ON 

DEHUMIDI-

FIER

dP

TF2

ON

TF1 - HYdP

Dove:

dP

:  dew point (see table 1).

TF1

:  second lower threshold of the dew point (expressed in °C).

TF2

:  first lower threshold of the dew point (expressed in °C).

HYdP

: dew point hysteresis equal to 0.5°C (cannot be modified).

On identification of the dew point temperature (table 1) which is to be 

respected, thresholds ‘ 

TF1

 ’ and ‘ 

TF2

 ’ will be set in order to obtain 

system adjustment such to prevent the formation of condensate.
Example:

dP > TF1 = the  dehumidification  system  starts  to  operate, 

maintaining the cooling system active if it has already 

been activated.

The following situation then occurs:

dP > TF2 = the  dehumidification  system  remains  active,  but  the 

cooling system is deactivated.

Once the value of ‘ 

TF2

 ’ is set lower than the minimum temperature 

of the cooling surface, this control allows to prevent the formation of 

condensate on the surface for any temperature and relative humidity 

value of the air.

ATTENTION

-  The maximum value of ‘ TF1 ’ will be self-limited to ‘ TF2 ’ less 

0.2°C.

- The ‘ TF2 ’ value must always be set with a value lower than 

the minimum temperature reached by the cooling surface to 

days (from 1 to 99).

At the end of the set number of hours or days, the programmable 

thermo-hygrostat will go back into the operating mode it was in prior 

to activation of the Vacation Program. While it is off, and in case the 

device has been set to Heating mode, the antifrost function will be in 

any case active, and the display will show the symbol ‘   ‘ and the 

countdown of the time remaining to the end of the program.
Note: Access to the vacation program will NOT be enabled while the 

‘ cleaning program ‘ is on.
To activate the vacation program proceed as follows:

1.

 Select the parameter ’

HOL

’ and press ’

OK

’; the display shows the 

symbol ‘   ‘, the indication ’h 00’ and the ‘ 

P

 

‘ icon flashing.

2.

 Press buttons ‘   ‘ and ‘   ‘ to set the vacation time; 

every 

change will be automatically memorized

.

  Up to 95 hours, the programming is indicated in hours and the 

display will show ‘ h XX ‘.

  Once that value is exceeded, the device will automatically switch to 

the mode for programming the vacation time in days and display will 

show ‘ d XX ‘. It will be possible to increase or decrease the hour 

or day by one unit at a time, with values ranging from 1 .. 95 hours 

and 4 .. 99 days.

3.

 To activate the holiday program for a given time, press again the 

OK

’ button or wait 10 seconds without pressing any key; the 

display showsthe ‘ 

 ’ icon flashing and the time remaining to the 

end of the holiday period.

 

If you have not set the time duration of the holiday (h:00), you can 

exit the adjustment and return to normal operation by pressing the 

‘ 

OK

 ’ or ‘   ‘ or by waiting 10 seconds without pressing any key.

4.

 To deactivate the vacation function and resume normal operation, 

press the button ‘   ‘.

H-C

’ HEATING / COOLING SETTING

This setting is used to invert the operating logic of the thermostat 

relay according to whether a heating or air conditioning unit is being 

controlled.

ATTENTION:

-  By modifying the relay operating logic, the setpoint values 

will be automatically taken back to the default values for the 

mode set.

-  The programmable thermo-hygrostat leaves the factory set in 

the heating mode.

To modify the operating logic, carry out the following procedure:

1.

 Select the parameter ’ 

H-C

 ’ and press ’ 

OK

 ’; the display shows the 

current adjustment mode and the ‘ 

P

 

‘ icon flashes.

2. 

Press thebuttons ‘   ’ and ‘   ’ to select thedesired adjustment; 

each change isautomatically saved

.

3.

 To return to the list of user parameters, press the ‘ 

OK 

’ button.

4.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

During normal operation, if the heating mode is on, the ‘   ‘ icon will 

remain lit, whereas if the cooling mode is on, the ‘   ‘ will remain 

steadily lit.

HYH

’ SETTING HYGROSTAT HYSTERESIS

Setting this parameter allows to define the hysteresis, in %RH, which 

is applied to the programmable thermo-hygrostat to adjust the room 

humidity, whenever the ‘ 

C-dP

 ‘ (dew point) user parameter has not 

been enabled.

To adjust the differential, perform the following operations:

1.

 Select the ‘ 

HYH

 ’ parameter and press ‘ 

OK

 ’.

2.

 The display will show the previously set value and the ‘ 

P

 

‘ icon 

will flash.

3.

 Press the ‘   ‘ and ‘   ‘ keys to modify the value (between 

0.5%RH .. 10.0%RH); 

every  modification  is  memorised 

automatically

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

OFSH

’  INTERNAL HUMIDITY SENSOR OFFSET SETTING

With this parameter it is possible to correct the humidity reading of 

the internal sensor by ±5%RH in order to correct any systematic 

reading errors due to the positioning of the programmable thermo-

hygrostat in areas unsuitable for measuring the room humidity. The 

device leaves the factory with the Offset set at  0.0%RH.

To adjust the Offset value for the internal sensor, carry out the 

following steps:

1. 

Select the ‘ 

OFS1

 ’ parameter and press ‘ 

OK

 ’.

2. 

The display will show the previously set Offset value and the ‘ 

P

 

‘ 

icon will flash.

3.

 Press the ‘   ‘ and ‘   ‘ keys to modify the value (between 

-5.0%RH .. +5.0%RH); 

every  modification  is  memorised 

automatically

.

4.

 To return to the list of user parameters, press the ‘

OK

’ button.

5.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

dE-H

’ DEHUMIDIFICATION/HUMIDIFICATION SETTING

This setting is used to invert the operating logic of the programmable 

thermo-hygrostat  relay  according  to  whether  a  dehumidification  or 

humidification device is being controlled.

ATTENTION:

-  The  dehumidification  function  is  not  active  in  the  heating 

mode.

Summary of Contents for 18002200

Page 1: ...icona e l icona SET RH a indicare che si sta visualizzando l umidit di setpoint Premere i tasti e per modificare l umidit di setpoint visualizzata Premere il tasto il display visualizza l umidit di ri...

Page 2: ...tainoreeildisplaymostrer h XX Superando tale valore si passer automaticamente alla programmazione del tempo di vacanze in giorni e il display mostrer d XX Sar possibile incrementare o decrementare l o...

Page 3: ...rrere tra due possibili azioni consecutive dei rel di uscita a seguito dell intervento della funzione c dP Il tempo di intervento incrementabile a passi di 3 minuti il tempo di intervento verr reinizi...

Page 4: ...NZIONE Il cronotermoigrostato al fine di ottimizzare la durata delle batterie rileva la temperatura ambiente ogni 3 minuti e di conseguenza decide l attivazione o disattivazione dei rel Per effettuare...

Page 5: ...in modalit Spento Antigelo C Tasto dalla tripla funzione Nel normale funzionamento visualizza l ora oppure la temperatura In Impostazione Programma orario imposta la regolazione della temperatura in...

Page 6: ...he wall plate using the supplied screw that is located inside the battery compartment Fig 8 5 Fig 8 Insert the batteries in the battery compartment I in Fig 1 see paragraph HOW TO INSERT REPLACE THE B...

Page 7: ...the current day is highlighted by a box surrounding the number corresponding to the day of the week 1 Monday 7 Sunday 8 Confirm by pressing OK the output of the time and day setting is automatic Time...

Page 8: ...button 5 To exit the user parameter settings and resume normal operation press the button or wait 10 seconds without pressing any key OFS2 REMOTE SENSOR OFFSET SETTING With this parameter it is possib...

Page 9: ...o di rugiada impostato nel sottoparametro d EC HYdP dew point hysteresis equal to 0 5 C cannot be modified d FP dew point control on fixed points If the dew point control function C dP is activated on...

Page 10: ...icators are lit inside the symbol If the symbol completely empty flashes it means that the batteries are depleted and must be replaced In this case both the relays are placed in the safety position N...

Page 11: ...ic ne et l ic ne SET RH indiquer que l humidit de consigne est affich e Appuyer sur les touches et pour modifier l humidit de consigne affich e Appuyer sur la touche l afficheur montrera l humidit de...

Page 12: ...es proc der de la mani re suivante 1 S lectionner le param tre HOL et appuyer sur la touche OK l afficheur montre le symbole l indication h 00 et l ic ne P clignotante 2 Appuyer sur les touches et pou...

Page 13: ...e temps d action peut tre augment par pas de 3 minutes et se remettra z ro chaque changement de modalit de r glage du point de ros e d EF d EC o d FP Cntr COMPTEUR D ACTIVATION DU RELAIS DU THERMOSTAT...

Page 14: ...er de la mani re suivante 1 Ouvrir le volet d acc s au logement des piles Fig 4 2 Extraire les piles en faisant levier avec un outil appropri 3 Ins rer les piles neuves qui doivent tre du type 1 5 V A...

Page 15: ...la sonde distance mais le r glage de la temp rature s effectue avec le capteur interne Clignotante L affichage et le r glage de la temp rature ambiante s effectuent avec l utilisation de la sonde dist...

Reviews: