INSTALLATION
The installation must be executed by a professional.
Note!
Mains supply requirements
High power equipment may, due to the primary current drawn from the mains supply, influence the
power quality of the grid. Therefore connection restrictions or requirements regarding the
maximum permissible mains impedance or the required minimum supply capacity at the interface
point to the public grid may apply for some types of equipment (see technical data). In this case it
is the responsibility of the installer or user of the equipment to ensure, by consultation with the
distrubution network operator if necessary, that the equipment may be connected.
5.1
Lifting instruction
5.2
Location
Position the welding power source such that its cooling air inlets and outlets are not
obstructed.
5.3
Mains power supply
Check that the welding power source is connected to the
correct mains power supply voltage, and that it is protected by
the correct fuse size. A protective earth connection must be
made in accordance with regulations.
Rating plate with supply connection data
Recommended fuse sizes and minimum cable area
Tig 3000i
TIG
MMA
Mains voltage
400 V 3
μ
50 Hz
400 V 3
μ
50 Hz
Mains cable area
mm
2
4G2,5
4G2,5
Phase current
I
1eff
8 A
13 A
Fuse
anti--surge
type C MCB
10 A
16 A
16 A
16 A