27
after no operation of more than 10S.
Note: It exists automatically from the current interface
after no operation of more than 10S.
The SYS value can only be modified under the non-lithium "USE" type. That is, the battery type is Sealed, Gel, or Flooded before entering the
"USE" type, the SYS value can be modified; if it is lithium battery type before entering the
"USE" type, the SYS value cannot be modified.
Only the above battery parameters can be set on the local controller, and the remaining battery parameters follow the following logic (the voltage
level of 12V system is 1, the voltage level of 24V system is 2
,
the voltage level of 48V system is 4).
Battery type
Battery parameters
Sealed/Gel/Flooded
User
LiFePO4 User
Li(NiCoMn)O2 User
Over voltage disconnect voltage
BCV+1.4V*voltage level
BCV+0.3V*voltage level
BCV+0.3V*voltage level
Charging limit voltage
BCV+0.6V*voltage level
BCV+0.1V*voltage level
BCV+0.1V*voltage level
Over voltage reconnect voltage
BCV+0.6V*voltage level
BCV+0.1V*voltage level
Boost charging voltage
Equalize charging voltage
BCV+0.2V*voltage level
Boost charging voltage
Boost charging voltage
Boost reconnect charging voltage
FCV-0.6V*voltage level
FCV-0.6V*voltage level
FCV-0.1V*voltage level
Under voltage warning reconnect voltage
UVW+0.2V*voltage level
UVW+0.2V*voltage level
UVW+1.7V*voltage level
Under voltage warning voltage
LVD+0.9V*voltage level
LVD+0.9V*voltage level
LVD+1.2V*voltage level
Discharging limit voltage
LVD-0.5V*voltage level
LVD-0.1V*voltage level
LVD-0.1V*voltage level