14
Battery Connection
Connecting a fuse in series through battery positive (+) in the circuit and the
battery circuit fuse must be 1.25 to 2 times to the rated current. Keep OFF
before connection. Connect battery positive (+) and negative (-) to battery
terminals on the controller in the figure 1-1. Please pay much att
ention to „+‟
and „-‟.
Solar Module(s) Connection
Connecting a breaker in series in the solar circuit is recommended, and the
breaker must be 1.25 to 2 times of the rated current. Keep OFF before
connection. Connect solar positive (+) and negative (-) to solar terminals on
the controller in the figure 1-
1. Please pay much attention to „+‟ and „-‟.
Solar array short circuit protection and the reversed polarity connection will
trigger automatically.
WARNING:
Risk of electric shock!
Use fuses or breakers in solar and battery circuits is recommended,
and make them keep OFF state before connection.
WARNING:
Risk of electric shock!
Exercise caution when handling solar wiring. The solar PV array can
produce open-circuit voltages in excess of 150 V when in sunlight.
Pay more attention to it.
Figure 2-2
Multi-machine Wiring Diagram