The control switch is found behind the rear
cover panel
Commissioning mode is chosen by
pressing the SET button for 4 seconds, all
sensor inputs will be disabled in this mode
so that they do not interfere with flow rates.
All LEDs will light with the Extract Boost
flashing, this indicates that the flow rate may
now be increased/decreased as required.
The next press of the SET button will move
commissioning to the next setting, Sup.B
and so on. When the unit has been fully
commissioned, press the SET button for 4
seconds and this will put the unit back into
status mode. If the unit is not put back into
status mode after commissioning, it will
automatically revert back to status mode
after an hour.
Note: Settings will be retained if the power
supply is interrupted.
Please note the supply fan is always
located at the top of the fan tower. If the
extract & supply flows appear to be reversed,
the fan connections on the PCB control may
need to be reversed (see instruction 1b).
In Status Mode the LEDs may indicate the
following information:
Setup guide for the energiSava 380
07
Commissioning Part 2
Commissioning Mode
LED 1 flashing
Extract Boost - Ext.B,
default start point
LED 2 solid
Supply Boost - Sup.B,
first press
LED 3 solid
Extract Trickle - Ext.T,
second press
LED 4 solid
Supply Trickle - Sup.T,
third press (fourth press
will move setting back
Ext.B)
Constant LED
Flashing LED
Frost protection
mode ON
Supply motor
has stopped
Boosted state -
Humidity ON
Extract motor
has stopped
Boosted state -
Switched input ON
N/A
Summer bypass
mode ON
Check filter*
*To reset filter indication, see maintenance
section on page 23.