Table 9: Orifice and Pressure Information.
EX32 With Log Set & Proflame Valve
Main Burner
Natural Gas
Propane Gas
Orifice:
#37 DMS
#52 DMS
Max. Manifold Press:
3.6 W.C. (0.89 KPa)
10.0” W.C. (2.49 KPa)
Min. Manifold Press:
1.6 W.C. (0.40 KPa)
6.4” W.C. (1.59 KPa)
Max.
Supply Press:
7.0” W.C. (1.74 KPa)
11.0” W.C. (2.74 KPa)
Min. Supply Press:
4.5” W.C. (1.12 KPa)
10.4” W.C. (2.59 KPa)
Max.
Input:
32,500 BTU/hr (9.52 KW)
31,000 BTU/hr (9.08 KW)
Min. Input:
21,000 BTU/hr (6.15 KW)
24,500 BTU/hr (7.18 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
a
Djusting
t
he
p
iLot
f
Lame
:
The pilot flow adjustment is set to maximum at the factory and should not need to be adjusted. The pilot
flame should envelope ⅜” to ½” (10 to 13mm) of the Flame sensor (see Figure 35). However, should the
need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through the front of the unit using a 10 inch long blade head
screw driver (see Figure 34 for location on valve).
2. Turn the adjustment screw clockwise to decrease or counterclockwise to increase pilot flame.
Figure 35: Proper Pilot Flame
.
Initial Installation
QUALIFIED INSTALLERS ONLY
.375-.500
(10-13mm)
Flame Sensor