Enviro EX32 Owner'S Manual Download Page 25

25

Initial Installation

QUALIFIED INSTALLERS ONLY

ICC

EXCELDirect

M&G

DirectVent 

Pro

Z-Flex

Vertical 

Termination

TM-SVT*

46DVA-VCH* See Liner 

Kit

TM-IVT

High-Wind 

Shield

TM-SVTS

46DVA-VWG

Flashing

TF-MFR

46DVA-GK

See Liner 

Kit

Co-Linear 

Adapter

TM-CTA

35’ Liner Kit

TM-ALK

46DVA-CL33 2DVI335X

35’ Flex Pipe     

(1 pce.)

TC-øAL35

3DFA-35

*

Requires co-linear adapter

Required when installed with minimum vent length

Table 8: Approved Terminations & other parts

4. Check that the chimney clean outs fit properly. The flue damper must be fully blocked open or removed 

for installation of the EX32; the smoke shelves, shields and baffles may be removed if attached by 

mechanical fasteners. 

5.  Stretch  the  Ø3”  (76mm)  flex  vent  liners  to  the 

length  needed  to  ensure  they  can  be  easily 

connected to the vent terminals.

6.  Install  the  flex  pipe  assembly  up  through  the 

chimney, ensure that the pipe slides through far 

enough  to  connect  onto  the  vent  cap.  Refer  to 

table 8 to confirm the vent cap is approved for 

use. 

7.  Most  vent  caps  can  be  installed  onto  chimneys 

with  flue  openings  up  to  16”  (406mm)  x  16” 

(406mm) when the actual flashing is 16” x 16” 

or larger. If the chimney is smaller, the flashing 

should be trimmed down and folded over.

8.  Apply a bead of stove cement sealant to the Ø3” 

(76mm) pipe of the exhaust vent terminal. Slide 

the flex liner onto the vent terminal and secure 

with three (3) sheet metal screws evenly spaced.

9.  Place a bead of high temperature silicone on the 

Table 7: Vent termination clearances

Minimum Clearance* 

Description

3 ft (0.9 m)

Clearance above the highest point where it passes through a roof surface, refer to 

Figure 23.

24 in (0.6 m)

Clearance above 

a roof ridge, any other portion of a building, or any other obstruc

-

tion within a horizontal distance of 10 feet (3 m), refer to Figure 23.

6 ft (1.83 m)

Clearance to mechanical air supply inlet.

3ft (0.9m) 

Clearance to each side of center line extended above meter/regulator assembly.

6 ft (1.83 m)

Radial clearance around service regulator vent outlet.

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

3 ft (0.9 m)

Clearance to a building opening or combustion air inlet of another appliance, ex-

cept with the approval of the authority having jurisdiction for the following reduced 

clearances.

9 in  (0.23 m)

Exception for inputs up to and including 50,000 Btu/h (15kW)

12 in (0.3 m)

Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000 

Btu/h (30kW)

*Clearances are in accordance with local installation codes and the requiremenets of the gas supplier

intake collar of the vent terminal. Slide the Ø3” (76mm) flex intake liner over the collar, secure the flex 

liner with three (3) sheet metal screws evenly spaced. Secure the vent terminal to the chimney using 

adequate sealant, and according to local building codes.

Summary of Contents for EX32

Page 1: ...sing property damage personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html 400...

Page 2: ...er s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Massachusetts in...

Page 3: ...must be performed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFP...

Page 4: ...16 Cleaning the Glass 17 Cleaning the Firebox 16 Replacing the Glass 17 Check Pilot and Burner Flames 17 Burner Removal 18 Ember Lights Bulb Replacement 19 Top Light Bulb Replacement 19 Fuel Conversio...

Page 5: ...Has been certified for use with either natural or propane gases See rating label Is not for use with solid fuels Is approved for bedroom or bed sitting room IN CANADA must be installed with a permane...

Page 6: ...the bottom of the unit Dimensions Install Depth The EX32 has a minimum install depth of 16 406mm The table below shows what depth of install is required with each surround panel Table 1 Install Depths...

Page 7: ...4 1022mm Depth Bottom 4 112mm Top 3 13 16 97mm 3 11 16 94mm Table 3 Elite Surround Options Surround Borderview Plus Borderview Plus Height 26 125 665mm 26 125 665mm Width 40 1016mm 40 1016mm Surround...

Page 8: ...to light the pilot by hand 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above on this label If you do...

Page 9: ...ch is a safety hazard Contact the dealer if there is any concern about the venturi adjustment Figure 4 Adjusting the venturi air setting The venturi adjustment lever is located on the right side of th...

Page 10: ...is powered by three 3 AAA type batteries A Mode Key is provided to Index between the features and a Thermostat Key is used to turn on off or index through Thermostat functions Figure 5 6 Figure 5 Prof...

Page 11: ...ith wiring harnesses The IFC is mainly powered by 120 VAC but can also run off a battery backup four 4 AA type batteries for shorter periods of time The IFC accepts commands via radio frequency from t...

Page 12: ...nstructions Turn off the Appliance Press the ON OFF Key on the Transmitter The Transmitter LCD display will only show the room temperature and Icon see Figure 9 A single beep from the IFC confirms rec...

Page 13: ...Maximum Flame Level Fan Control The EX32 comes with a convection fan that can be controlled with the Transmitter The fan speed can be adjusted thorugh six 6 speeds To control the fan press the MODE k...

Page 14: ...the IFC will confirm the command has been received The top light is most noticable when the flame is set to the lowest setting It can also be left on when the flame is off see Remote Flame Control se...

Page 15: ...iance burner when operating the remote system Operating Instructions WARNING Shock Hazard Can cause severe injury or death This device is powered by line voltage Do not try to repair this device In no...

Page 16: ...ainted Surfaces Painted surfaces should be periodically wiped with a damp cloth when the unit is cool Figure 19 A Door Spring Latch Locations The glass door of the fireplace is retained at the top by...

Page 17: ...the dealer Check the logs for deterioration or large amounts of soot a small amount on the logs is normal Replace the logs and embers as in the Secondary Installation Log Set and Ember Installation s...

Page 18: ...tenance and Service Glass Door Removal 2 Carefully remove the log set and embers as shown in Secondary Installation Log Set Installation 3 Remove the four log tray screws using a T20 screwdriver then...

Page 19: ...transmitter turn off the ember lights see page 13 2 Remove the burner as outlined in Maintenance and Service Burner Removal 3 Remove the light tray by simply lifting up and out 4 Replace the burnt out...

Page 20: ...ontact your dealer distributor or courier company to have them replaced before starting this installation Maintenance And Service Conversion Kit Installation 1 Turn the unit off by pressing the ON OFF...

Page 21: ...led at an altitude higher than 2000ft 610m it is required to de rate the unit accordingly In the USA The appliance may be installed at higher altitudes Please refer to your American Gas Association gu...

Page 22: ...th Fireplace Dimensions 28 711 mm 18 1 2 470 mm 20 508 mm 16 406 mm NOTE Space must be provided for gas line on right side of unit for servicing purposes Venting WARNING This appliance has been design...

Page 23: ...eplace prior to installation Initial Installation QUALIFIED INSTALLERS ONLY The ENVIRO EX32 may be installed and vented into any solid fuel fireplace that has been installed in accordance with the Nat...

Page 24: ...installed and vented into any solid fuel fireplace that has been installed in accordance with the National Provincial State and local building codes and has been constructed of non combustible materi...

Page 25: ...rminal Slide the flex liner onto the vent terminal and secure with three 3 sheet metal screws evenly spaced 9 Place a bead of high temperature silicone on the Table 7 Vent termination clearances Minim...

Page 26: ...ace a bead of high temperature silicone on the intake collar of the fireplace slide the 3 76mm flex intake liner over the collar secure the flex liner with three 3 sheet metal screws evenly spaced 13...

Page 27: ...floor is prohibited The included label plate shown below must be permanently attached inside the cavity of the fireplace in a visible location WARNING This fireplace has been converted for the use wit...

Page 28: ...LLERS ONLY Figure 33 Wiring Schematic IFC Main Harness Transmitter TMFLSA 885 Gas Valve IPI Pilot Convection Fan Proflame 2 System Wiring Diagram Main On Off Power Cord To Battery Holder Flame Sensor...

Page 29: ...I D hose over pressure tap system Check pressures using a manometer When finished release pressure remove hose tighten set screw Gas Line Connection Prior to installation consult your local authoriti...

Page 30: ...18 KW NEVER USE AN OPEN FLAME FOR LEAK TESTING Adjusting The Pilot Flame The pilot flow adjustment is set to maximum at the factory and should not need to be adjusted The pilot flame should envelope t...

Page 31: ...tions excluding 4 sided and it may also be used with the trimmable Surround The Base Shelf and Riser are sold separately Installation 1 If unit is running turn it off and allow it to cool completely 2...

Page 32: ...beginning this installation Height Width 3 Sided Surround 25 635 mm 39 7 8 1013 mm 4 Sided Surround 31 1 2 800 mm 39 7 8 1013 mm Table 10 Surround Dimensions Please check components supplied with this...

Page 33: ...rect measurements of offset and remove any sharp edges 5 The panel can be touched up with a high temperature metallic black paint available from your dealer INSTALLATION 1 Install the two Trimmable Pa...

Page 34: ...2 Next install the back log as shown in Figure 45 and position it all the way to the right The right front corner will rest on the triangle support when installed correctly Then fill the front ember...

Page 35: ...ond Right Top Logs Figure 50 Nuggets and Ember Wool 6 Next Install the left and second right top log as shown in Figure 49 Note the locating notches on the bottom side of both logs areas highlighted T...

Page 36: ...at ALL the burner ports If a long delay is noticed turn the appliance off and wait for it to cool down Then remove the glass and make sure none of the burner ports are blocked Maintenance Once a year...

Page 37: ...will blink one 1 time in intervals 3 Parasitic Pilot Flame the LED indicator will blink two 2 times in intervals 4 System Lock out the LED indicator will blink three 3 times in intervals Additional I...

Page 38: ...type settings on the valve and pilot burner assembly orifice Pilot will not remain lit Problem with Flame Sensor circuit Check for proper connection of the Flame Sensor to the IFC board Check pilot f...

Page 39: ...r temperature Flame lifting Leak in vent pipe Check for leaks in vent connections Improper vent configuration Check vent configuration with manual Terminal may be re circulating flue gases Check to se...

Page 40: ...09 Ledgstone Liner Set 50 2774 Porcelain Liner Set 50 2427 15 EX32 EX35 Pilot Shield 50 3514 16 EX32 Stainless Steel Baffle 50 3527 17 Top Light Assembly 50 3516 18 Fan Only 50 2493 19 Proflame 2 IFC...

Page 41: ...41 Parts Diagram Components 16 12 11 10 9 8 7 15 6 23 14 17 3 4 5 18 22 19 20 21 2 1 13 24 25 26 27...

Page 42: ...42 Notes...

Page 43: ...ty screen mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused from...

Page 44: ...__________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy DIR...

Reviews: