Enviro EG31 Nova Owner'S Manual Download Page 30

Trouble Shooting

Problem

Possible Cause

Solution

The  main  burner 

does  not  ignite 

when called for.

The gas valve may not be on.

• Check that the gas control knob is in the “ON” position.

Thermostat is not calling for 

heat.

• Adjust the thermostat several degrees above ambient temperature.

Problem with gas valve.

• Use a DC voltmeter to measure the voltage across the TPTH and 

TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed 

circuit ≥ 100mV

• If voltage is not present, check the control circuit for proper 

operation.

• If proper control system voltage is present, replace the gas control.

Spark will not 

light the pilot 

after repeatedly 

pressing the 

spark ignitor.

Defective piezo ignitor.

• Check connections to ignitor.

• If ignitor connections are good but no spark, replace ignitor.

Broken spark electrode.

• Check for broken ceramic insulation, replace electrode if broken.

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot, loosen the screws on the 

pilot base adjust and tighten.

Pilot will not 

remain lit.

Problem with thermocouple 

circuit.

• Check for proper connection of the thermocouple to the rear of the 

valve. If loose, fully tighten.

• Check pilot for full flame impingement around thermocouple.  If flame 

is too small, check gas pressure, adjust pilot rate screw, check pilot 

head for damage.

• Check thermocouple voltage at valve. It must be greater than 5 mV.  

If low, replace thermocouple.

Air in gas line (pilot dies while 

knob is depressed).

• Bleed line.

• Check gas line pressure.

• Contact dealer.

Burners will not 

remain lit.

Problem with thermopile 

circuit.

• Check gas line pressure .

• Check for flame impingement on thermopile. If low, see “Pilot will not 

remain lit”.

• Check thermopile for minimum of 300 mV when burner is switched 

on.

• Check wiring to thermostat for breaks.

BV ONLY: 

Check for spillage at draft hood that may trip spill switch

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

Improper vent configuration

• Check vent configuration with manual.

Terminal may be recirculating 

flue gases

• Check to see if terminal is on correctly.

• May need to install high wind termination cap.

• Contact dealer.

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

Flames are 

burning “dirty” or 

sooting

Flame impingement

• Check log positioning.

• Increase primary air by opening the venturi shutter and/or by 

opening the vent restrictor.

See also “Burners will not remain lit.”

Remote control 

doesn’t work

Problem with the remote

• One or more of the batteries are dead. See remote control 

instructions.

Problem with fireplace

• The on/off switch is turned to OFF.

• The gas control valve is turned to PILOT or OFF.

• The pilot has gone out.

BV ONLY: 

Insufficient air 

for combustion

• Air tight house.

•  A  vacuum  in  room  due  to 

other air-moving device.

• Supply make up air to the unit.

30

Summary of Contents for EG31 Nova

Page 1: ...personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier W A R R A N T Y R E G I S T R A T I O N e n v i r o c o m w a r r...

Page 2: ...ll your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali...

Page 3: ...erformed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or t...

Page 4: ...ze 14 Direct Vent Model 15 Direct Vent Restrictor Ring 15 Venting Fireplace Inserts 15 Automatic Flue Gas Spill Switch 17 Direct Vent Vertical Vent Termination 18 B Vent Model 19 Converting A Direct V...

Page 5: ...G METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY This ENVIRO EG31 Fireplace Has been certified for use with either natural or propane gases See rating label Is not for use with solid fuels Is approv...

Page 6: ...30 39 93 13 99 28 25 2 13 16 14 OR 14 41 18 27 OR 16 54 21 75 19 52 Install Depth If the available depth of install is less than the 16 14 shown above the stove depth can be reduced to 14 41 by removi...

Page 7: ...re or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and...

Page 8: ...minutes The speed of the fan can be changed by turning the fan control knob To turn the blower off turn the knob COUNTER CLOCKWISE until it clicks off It is advisable not to operate the blower below 1...

Page 9: ...s cooled remove the face of the fireplace along with the glass See Maintenance And Service Glass Door Removal Check the gasket material on the back of the glass making sure that it is attached and int...

Page 10: ...s located in the center of the burner tray see Figure 7 Slide tray to the left and lift out 3 Remove brick panels see Secondary Installation Brick Panels Installation 4 Remove the surround panel by li...

Page 11: ...ed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation...

Page 12: ...and glass door Also refer to Secondary Installation Installing Log Set and Embers When re installing the burner ensure that the burner to pilot hood relationship is similar to what is shown in Figure...

Page 13: ...as been installed at an altitude higher than 2000ft 610m it is required to de rate the unit accordingly In the USA The appliance may be installed at higher altitudes Please refer to your American Gas...

Page 14: ...mm from the bottom of unit If installed at floor level there must be a minimum of 16 406 mm of non combustible material in front of the unit Minimum ceiling clearance is 61 5 1562mm from bottom of un...

Page 15: ...m Use the vent restrictor ring for installations above 15 feet 4 57 m See Figure 14 for installation of restrictor ring Venting Fireplace Inserts The ENVIRO EG31 may be installed and vented into any...

Page 16: ...ch side of center line extended above meter regulator assembly 6 ft 1 83 m Radial clearance around service regulator vent outlet 12 in 30 cm Clearance above grade verandah porch deck or balcony 3 ft 0...

Page 17: ...is heater is equipped with a vent safety shutoff system designed to protect against improper venting of combustion products This safety switch is located on the rear of the appliance close to the draf...

Page 18: ...m flex vent over the flue collar and secure with three 3 sheet metal screws evenly spaced Note If fireplace opening is lower than 21 75 552 mm remove the vent collar plate from the top of the insert s...

Page 19: ...eplace To A Direct Vented Fireplace Parts required for conversion 1 Drafthood 2 3 dual pipe chimney connector 2 Air channel cover plates 1 Drafthood cover plate 1 Remove the chimney connector 300 spil...

Page 20: ...nscrewing the T 20 Torx screw located on the center top of the stove Slide collar plate backwards Properly secure the vent collar plate to the flexible vent pipe liner s previously installed in the ch...

Page 21: ...GINAL FIREPLACE MAY NEVER BE RETURNED TO SOLID FUEL USE IN THIS CONDITION IMPORTANT If the factory built fireplace has no gas access hole s provided an access hole of 1 5 inch 37 5 mm or less may be d...

Page 22: ...equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong...

Page 23: ...d from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at pressures equal to or less than psig 3 45 KPa Always...

Page 24: ...uld the need arise follow Steps 1 2 below Figure 27 Proper Pilot Flame 3 8 1 2 10 13mm Thermocouple Proper Flame Adjustment Initial Installation QUALIFIED INSTALLERS ONLY 1 The adjustment screw can be...

Page 25: ...n brackets will need to be removed as outlined in steps 1 3 below Secondary Installation Extension Brackets Removal REMOVAL 1 Using a T20 screwdriver remove the four 4 screws that secure the Top Exten...

Page 26: ...are still installed Safety Screen Assembly 1 Attach the left right top bottom brackets onto the safety screen using a T20 screwdriver and the supplied sixteen 16 8 T20 screws see Figure 30 Do not over...

Page 27: ...Installation Warning The surround becomes hot when the unit is operating ensure that the unit is turned off and that it has cooled to room temperature before begining this installation The safety scre...

Page 28: ...tip to tip on the rest area One end of the big log twig will rest on the pin on the right log and the other will lay within the left rest area The small log twig should be placed so it sit completely...

Page 29: ...left then up Gently pull right brick side panel inward from the bottom back Pull towards the back then out freeing it from the front retainer Caution The pilot may damage panel Remove left side panel...

Page 30: ...replace thermocouple Air in gas line pilot dies while knob is depressed Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pr...

Page 31: ...Orifice LP Threaded EC 020 3 Pilot Gasket EC 021 4 S I T Piezo Ignitor EC 023 Stainless Steel Flex Connector with Elbow 18 Long EC 024 5 FPI Burner Switch EC 026 6 FPI Fan Controller 115 V EC 039 6 F...

Page 32: ...Relief Door Gasket 30 034 14 Blank Orifice 73 50 343 BV Flue Collar Gasket 50 528 DV Flue Collar Gasket 50 529 Log Set Embers 50 588 15 Ceramic Brick Liner 50 610 Dual Bulb Door Gasket 10 feet 50 634...

Page 33: ...33 Parts Diagram Body Focus Components March 2008 14 15 16 2 1 3 17 4 5 6 7 8 10 9 11 12 13 18 EG31 Components...

Page 34: ...Notes 34...

Page 35: ...ler including serial number This warranty does not cover any discoloration of the safety screen mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This wa...

Page 36: ...____________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy N...

Reviews: